Siemens SCALANCE LPE9403

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 8.7
ATTENTION: Exploitable remotely/low attack complexity
Vendor: Siemens
Equipment: SCALANCE LPE9403
Vulnerabilities: Improper Neutralization of Special Elements used in an OS Command (‘OS Command Injection’), Improper Limitation of a Pathname to a Restricted Directory (‘Path Traversal’), Improper Check for Dropped Privileges

2. RISK EVALUATION
Successful exploitation of these vulnerabilities allow a remote attacker to execute arbitrary code, read and write arbitrary files, escalate privileges, or execute a limited set of binaries that are present on the filesystem
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:

SCALANCE LPE9403 (6GK5998-3GS00-2AC2): Versions prior to V4.0

3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78
Affected devices do not properly sanitize user input when creating new VXLAN configurations. This could allow an authenticated highly-privileged remote attacker to execute arbitrary code on the device.
CVE-2025-27392 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-27392. A base score of 8.6 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.2 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78
Affected devices do not properly sanitize user input when creating new users. This could allow an authenticated highly-privileged remote attacker to execute arbitrary code on the device.
CVE-2025-27393 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-27393. A base score of 8.6 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.3 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78
Affected devices do not properly sanitize user input when creating new SNMP users. This could allow an authenticated highly-privileged remote attacker to execute arbitrary code on the device.
CVE-2025-27394 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-27394. A base score of 8.6 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.4 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22
Affected devices do not properly limit the scope of files accessible through and the privileges of the SFTP functionality. This could allow an authenticated highly-privileged remote attacker to read and write arbitrary files.
CVE-2025-27395 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-27395. A base score of 8.6 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.5 IMPROPER CHECK FOR DROPPED PRIVILEGES CWE-273
Affected devices do not properly limit the elevation of privileges required to perform certain valid functionality. This could allow an authenticated lowly-privileged remote attacker to escalate their privileges.
CVE-2025-27396 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-27396. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.6 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22
Affected devices do not properly limit user controlled paths to which logs are written and from where they are read. This could allow an authenticated highly-privileged remote attacker to read and write arbitrary files in the filesystem, if and only if the malicious path ends with ‘log’ .
CVE-2025-27397 has been assigned to this vulnerability. A CVSS v3 base score of 3.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:N).
A CVSS v4 score has also been calculated for CVE-2025-27397. A base score of 5.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:L/VI:L/VA:N/SC:N/SI:N/SA:N).
3.2.7 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78
Affected devices do not properly neutralize special characters when interpreting user controlled log paths. This could allow an authenticated highly-privileged remote attacker to execute a limited set of binaries that are already present on the filesystem.
CVE-2025-27398 has been assigned to this vulnerability. A CVSS v3 base score of 2.7 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:L/A:N).
A CVSS v4 score has also been calculated for CVE-2025-27398. A base score of 2.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:P/PR:H/UI:N/VC:N/VI:L/VA:N/SC:N/SI:N/SA:N).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
Siemens reported these vulnerabilities to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

SCALANCE LPE9403 (6GK5998-3GS00-2AC2): Update to V4.0 or later version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-075201 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:

Do not click web links or open attachments in unsolicited email messages.
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY

March 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SCALANCE LPE9403
  • Vulnerabilities: Improper Neutralization of Special Elements used in an OS Command (‘OS Command Injection’), Improper Limitation of a Pathname to a Restricted Directory (‘Path Traversal’), Improper Check for Dropped Privileges

2. RISK EVALUATION

Successful exploitation of these vulnerabilities allow a remote attacker to execute arbitrary code, read and write arbitrary files, escalate privileges, or execute a limited set of binaries that are present on the filesystem

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • SCALANCE LPE9403 (6GK5998-3GS00-2AC2): Versions prior to V4.0

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78

Affected devices do not properly sanitize user input when creating new VXLAN configurations. This could allow an authenticated highly-privileged remote attacker to execute arbitrary code on the device.

CVE-2025-27392 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-27392. A base score of 8.6 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78

Affected devices do not properly sanitize user input when creating new users. This could allow an authenticated highly-privileged remote attacker to execute arbitrary code on the device.

CVE-2025-27393 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-27393. A base score of 8.6 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.3 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78

Affected devices do not properly sanitize user input when creating new SNMP users. This could allow an authenticated highly-privileged remote attacker to execute arbitrary code on the device.

CVE-2025-27394 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-27394. A base score of 8.6 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.4 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22

Affected devices do not properly limit the scope of files accessible through and the privileges of the SFTP functionality. This could allow an authenticated highly-privileged remote attacker to read and write arbitrary files.

CVE-2025-27395 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-27395. A base score of 8.6 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.5 IMPROPER CHECK FOR DROPPED PRIVILEGES CWE-273

Affected devices do not properly limit the elevation of privileges required to perform certain valid functionality. This could allow an authenticated lowly-privileged remote attacker to escalate their privileges.

CVE-2025-27396 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-27396. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.6 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22

Affected devices do not properly limit user controlled paths to which logs are written and from where they are read. This could allow an authenticated highly-privileged remote attacker to read and write arbitrary files in the filesystem, if and only if the malicious path ends with ‘log’ .

CVE-2025-27397 has been assigned to this vulnerability. A CVSS v3 base score of 3.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:N).

A CVSS v4 score has also been calculated for CVE-2025-27397. A base score of 5.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:L/VI:L/VA:N/SC:N/SI:N/SA:N).

3.2.7 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78

Affected devices do not properly neutralize special characters when interpreting user controlled log paths. This could allow an authenticated highly-privileged remote attacker to execute a limited set of binaries that are already present on the filesystem.

CVE-2025-27398 has been assigned to this vulnerability. A CVSS v3 base score of 2.7 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:L/A:N).

A CVSS v4 score has also been calculated for CVE-2025-27398. A base score of 2.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:P/PR:H/UI:N/VC:N/VI:L/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • SCALANCE LPE9403 (6GK5998-3GS00-2AC2): Update to V4.0 or later version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-075201 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • March 13, 2025: Initial Publication

 Read More

Siemens SINEMA Remote Connect Client

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 9.3
ATTENTION: Exploitable remotely/low attack complexity
Vendor: Siemens
Equipment: SINEMA Remote Connect Client
Vulnerabilities: Integer Overflow or Wraparound, Unprotected Alternate Channel, Improper Restriction of Communication Channel to Intended Endpoints, Stack-based Buffer Overflow, Unrestricted Upload of File with Dangerous Type, Missing Release of Resource after Effective Lifetime

2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to overflow memory buffers, impersonate a legitimate user, maintain longer session times, gain elevated privileges, and execute code remotely.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:

Siemens SINEMA Remote Connect Client: All versions below V3.2 SP3

3.2 VULNERABILITY OVERVIEW
3.2.1 INTEGER OVERFLOW OR WRAPAROUND CWE-190
The tap-windows6 driver version 9.26 and earlier does not properly check the size data of incoming write operations which an attacker can use to overflow memory buffers, resulting in a bug check and potentially arbitrary code execution in kernel space.
CVE-2024-1305 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-1305. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.2 UNPROTECTED ALTERNATE CHANNEL CWE-420
If an attacker with SeImeprsonatePrivilege manages to create a named pipe server with a name matching that used by the “Interactive Service”, user interfaces such as OpenVPN-GUI connecting to it could allow the attacker to impersonate the user running the UI.
CVE-2024-4877 has been assigned to this vulnerability. A CVSS v3 base score of 4.9 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:N).
A CVSS v4 score has also been calculated for CVE-2024-4877. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).
3.2.3 IMPROPER RESTRICTION OF COMMUNICATION CHANNEL TO INTENDED ENDPOINTS CWE-923
The interactive service in OpenVPN 2.6.9 and earlier allows the OpenVPN service pipe to be accessed remotely which allows a remote attacker to interact with the privileged OpenVPN interactive service.
CVE-2024-24974 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).
A CVSS v4 score has also been calculated for CVE-2024-24974. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).
3.2.4 STACK-BASED BUFFER OVERFLOW CWE-121
The interactive service in OpenVPN 2.6.9 and earlier allows an attacker to send data causing a stack overflow which can be used to execute arbitrary code with more privileges.
CVE-2024-27459 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-27459. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.5 UNRESTRICTED UPLOAD OF FILE WITH DANGEROUS TYPE CWE-434
OpenVPN plug-ins on Windows with OpenVPN 2.6.9 and earlier could be loaded from any directory which allows an attacker to load an arbitrary plug-in which can be used to interact with the privileged OpenVPN interactive service.
CVE-2024-27903 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-27903. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.6 MISSING RELEASE OF RESOURCE AFTER EFFECTIVE LIFETIME CWE-772
OpenVPN from 2.6.0 through 2.6.10 in a server role accepts multiple exit notifications from authenticated clients which will extend the validity of a closing session.
CVE-2024-28882 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N).
A CVSS v4 score has also been calculated for CVE-2024-28882. A base score of 7.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Commercial Facilities, Energy, Food and Agriculture, Healthcare and Public Health, Transportation Systems, Water and Wastewater Systems
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
Siemens reported these vulnerabilities to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

SINEMA Remote Connect Client: Update to V3.2 SP3 or later version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-615740 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY

March 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SINEMA Remote Connect Client
  • Vulnerabilities: Integer Overflow or Wraparound, Unprotected Alternate Channel, Improper Restriction of Communication Channel to Intended Endpoints, Stack-based Buffer Overflow, Unrestricted Upload of File with Dangerous Type, Missing Release of Resource after Effective Lifetime

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to overflow memory buffers, impersonate a legitimate user, maintain longer session times, gain elevated privileges, and execute code remotely.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • Siemens SINEMA Remote Connect Client: All versions below V3.2 SP3

3.2 VULNERABILITY OVERVIEW

3.2.1 INTEGER OVERFLOW OR WRAPAROUND CWE-190

The tap-windows6 driver version 9.26 and earlier does not properly check the size data of incoming write operations which an attacker can use to overflow memory buffers, resulting in a bug check and potentially arbitrary code execution in kernel space.

CVE-2024-1305 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-1305. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 UNPROTECTED ALTERNATE CHANNEL CWE-420

If an attacker with SeImeprsonatePrivilege manages to create a named pipe server with a name matching that used by the “Interactive Service”, user interfaces such as OpenVPN-GUI connecting to it could allow the attacker to impersonate the user running the UI.

CVE-2024-4877 has been assigned to this vulnerability. A CVSS v3 base score of 4.9 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2024-4877. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.2.3 IMPROPER RESTRICTION OF COMMUNICATION CHANNEL TO INTENDED ENDPOINTS CWE-923

The interactive service in OpenVPN 2.6.9 and earlier allows the OpenVPN service pipe to be accessed remotely which allows a remote attacker to interact with the privileged OpenVPN interactive service.

CVE-2024-24974 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2024-24974. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.2.4 STACK-BASED BUFFER OVERFLOW CWE-121

The interactive service in OpenVPN 2.6.9 and earlier allows an attacker to send data causing a stack overflow which can be used to execute arbitrary code with more privileges.

CVE-2024-27459 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-27459. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.5 UNRESTRICTED UPLOAD OF FILE WITH DANGEROUS TYPE CWE-434

OpenVPN plug-ins on Windows with OpenVPN 2.6.9 and earlier could be loaded from any directory which allows an attacker to load an arbitrary plug-in which can be used to interact with the privileged OpenVPN interactive service.

CVE-2024-27903 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-27903. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.6 MISSING RELEASE OF RESOURCE AFTER EFFECTIVE LIFETIME CWE-772

OpenVPN from 2.6.0 through 2.6.10 in a server role accepts multiple exit notifications from authenticated clients which will extend the validity of a closing session.

CVE-2024-28882 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2024-28882. A base score of 7.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Commercial Facilities, Energy, Food and Agriculture, Healthcare and Public Health, Transportation Systems, Water and Wastewater Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-615740 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • March 13, 2025: Initial Publication

 Read More

Siemens Tecnomatix Plant Simulation

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 7.0
ATTENTION: Low attack complexity
Vendor: Siemens
Equipment: Tecnomatix Plant Simulation
Vulnerabilities: Files or Directories Accessible to External Parties

2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an unauthorized attacker to read or delete arbitrary files or the entire file system of the device.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:

Siemens Tecnomatix Plant Simulation V2302: All versions prior to V2302.0021
Siemens Tecnomatix Plant Simulation V2404: All versions prior to V2404.0010

3.2 VULNERABILITY OVERVIEW
3.2.1 FILES OR DIRECTORIES ACCESSIBLE TO EXTERNAL PARTIES CWE-552
The affected application does not properly restrict access to the file deletion functionality. This could allow an unauthorized attacker to delete files even when access to the system should be prohibited, resulting in potential data loss or unauthorized modification of system files.
CVE-2025-25266 has been assigned to this vulnerability. A CVSS v3 base score of 6.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:L).
A CVSS v4 score has also been calculated for CVE-2025-25266. A base score of 7.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:L/SC:N/SI:N/SA:N).
3.2.2 FILES OR DIRECTORIES ACCESSIBLE TO EXTERNAL PARTIES CWE-552
The affected application does not properly restrict the scope of files accessible to the simulation model. This could allow an unauthorized attacker to compromise the confidentiality of the system.
CVE-2025-25267 has been assigned to this vulnerability. A CVSS v3 base score of 6.2 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).
A CVSS v4 score has also been calculated for CVE-2025-25267. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
Siemens reported these vulnerabilities to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

Tecnomatix Plant Simulation V2302: Update to V2302.0021 or later version
Tecnomatix Plant Simulation V2404: Update to V2404.0010 or later version

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-507653 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:

Do not click web links or open attachments in unsolicited email messages.
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.
5. UPDATE HISTORY

March 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.0
  • ATTENTION: Low attack complexity
  • Vendor: Siemens
  • Equipment: Tecnomatix Plant Simulation
  • Vulnerabilities: Files or Directories Accessible to External Parties

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an unauthorized attacker to read or delete arbitrary files or the entire file system of the device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • Siemens Tecnomatix Plant Simulation V2302: All versions prior to V2302.0021
  • Siemens Tecnomatix Plant Simulation V2404: All versions prior to V2404.0010

3.2 VULNERABILITY OVERVIEW

3.2.1 FILES OR DIRECTORIES ACCESSIBLE TO EXTERNAL PARTIES CWE-552

The affected application does not properly restrict access to the file deletion functionality. This could allow an unauthorized attacker to delete files even when access to the system should be prohibited, resulting in potential data loss or unauthorized modification of system files.

CVE-2025-25266 has been assigned to this vulnerability. A CVSS v3 base score of 6.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:L).

A CVSS v4 score has also been calculated for CVE-2025-25266. A base score of 7.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:L/SC:N/SI:N/SA:N).

3.2.2 FILES OR DIRECTORIES ACCESSIBLE TO EXTERNAL PARTIES CWE-552

The affected application does not properly restrict the scope of files accessible to the simulation model. This could allow an unauthorized attacker to compromise the confidentiality of the system.

CVE-2025-25267 has been assigned to this vulnerability. A CVSS v3 base score of 6.2 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2025-25267. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • Tecnomatix Plant Simulation V2302: Update to V2302.0021 or later version
  • Tecnomatix Plant Simulation V2404: Update to V2404.0010 or later version

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-507653 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.

5. UPDATE HISTORY

  • March 13, 2025: Initial Publication

 Read More

Siemens SINEMA Remote Connect Server

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 7.1
ATTENTION: Exploitable remotely/low attack complexity
Vendor: Siemens
Equipment: SINEMA Remote Connect Server
Vulnerabilities: Improper Output Neutralization for Logs, Missing Release of Resource after Effective Lifetime

2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to send garbage to OpenVPN log, cause high CPU load, or extend the validity of a closing session.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports the following products are affected:

SINEMA Remote Connect Server: Versions prior to V3.2 SP3

3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER OUTPUT NEUTRALIZATION FOR LOGS CWE-117
A malicious openvpn peer can send garbage to OpenVPN log or cause high CPU load.
CVE-2024-5594 has been assigned to this vulnerability. A CVSS v3 base score of 5.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:L/A:L).
A CVSS v4 score has also been calculated for CVE-2024-5594. A base score of 5.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:L/VA:L/SC:N/SI:N/SA:N).
3.2.2 MISSING RELEASE OF RESOURCE AFTER EFFECTIVE LIFETIME CWE-772
OpenVPN from 2.6.0 through 2.6.10 in a server role accepts multiple exit notifications from authenticated clients which will extend the validity of a closing session.
CVE-2024-28882 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N).
A CVSS v4 score has also been calculated for CVE-2024-28882. A base score of 7.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, Energy, Food and Agriculture, Healthcare and Public Health, Transportation Systems, Water and Wastewater Systems
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
Siemens reported these vulnerabilities to CISA.
4. MITIGATIONS
Siemens has released a new version for SINEMA Remote Connect Server and recommends updating to V3.2 SP3 or later version.
As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-073066 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY

March 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.1
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SINEMA Remote Connect Server
  • Vulnerabilities: Improper Output Neutralization for Logs, Missing Release of Resource after Effective Lifetime

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to send garbage to OpenVPN log, cause high CPU load, or extend the validity of a closing session.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports the following products are affected:

  • SINEMA Remote Connect Server: Versions prior to V3.2 SP3

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER OUTPUT NEUTRALIZATION FOR LOGS CWE-117

A malicious openvpn peer can send garbage to OpenVPN log or cause high CPU load.

CVE-2024-5594 has been assigned to this vulnerability. A CVSS v3 base score of 5.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:L/A:L).

A CVSS v4 score has also been calculated for CVE-2024-5594. A base score of 5.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:L/VA:L/SC:N/SI:N/SA:N).

3.2.2 MISSING RELEASE OF RESOURCE AFTER EFFECTIVE LIFETIME CWE-772

OpenVPN from 2.6.0 through 2.6.10 in a server role accepts multiple exit notifications from authenticated clients which will extend the validity of a closing session.

CVE-2024-28882 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2024-28882. A base score of 7.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, Energy, Food and Agriculture, Healthcare and Public Health, Transportation Systems, Water and Wastewater Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has released a new version for SINEMA Remote Connect Server and recommends updating to V3.2 SP3 or later version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-073066 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • March 13, 2025: Initial Publication

 Read More

Siemens SIMATIC S7-1500 TM MFP

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v3 7.8
ATTENTION: Low attack complexity
Vendor: Siemens
Equipment: SIMATIC S7-1500 TM MFP
Vulnerabilities: Double Free, Use After Free, NULL Pointer Dereference, Buffer Access with Incorrect Length Value, Use of Uninitialized Variable

2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to execute arbitrary code, cause a denial-of-service condition, or gain unauthorized access to sensitive information.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:

SIMATIC S7-1500 TM MFP – BIOS: All versions

3.2 VULNERABILITY OVERVIEW
3.2.1 DOUBLE FREE CWE-415
In the Linux kernel, the following vulnerability has been resolved: net: ethernet: lantiq_etop: fix double free in detach. The number of the currently released descriptor is never incremented, which results in the same skb being released multiple times.
CVE-2024-41046 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.2 USE AFTER FREE CWE-416
In the Linux kernel, the following vulnerability has been resolved: filelock: fix potential use-after-free in posix_lock_inode Light Hsieh reported a KASAN UAF warning in trace_posix_lock_inode(). The request pointer had been changed earlier to point to a lock entry that was added to the inode’s list. However, before the tracepoint could fire, another task raced in and freed that lock. Fix this by moving the tracepoint inside the spinlock, which should ensure that this doesn’t happen.
CVE-2024-41049 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).
3.2.3 NULL POINTER DEREFERENCE CWE-476
In the Linux kernel, the following vulnerability has been resolved: mm: prevent derefencing NULL ptr in pfn_section_valid() Commit 5ec8e8ea8b77 (“mm/sparsemem: fix race in accessing memory_section->usage”) changed pfn_section_valid() to add a READ_ONCE() call around “ms->usage” to fix a race with section_deactivate() where ms->usage can be cleared. The READ_ONCE() call, by itself, is not enough to prevent NULL pointer dereference. We need to check its value before dereferencing it.
CVE-2024-41055 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.4 BUFFER ACCESS WITH INCORRECT LENGTH VALUE CWE-805
In the Linux kernel, the following vulnerability has been resolved: tcp_metrics: validate source addr length I don’t see anything checking that TCP_METRICS_ATTR_SADDR_IPV4 is at least 4 bytes long, and the policy doesn’t have an entry for this attribute at all (neither does it for IPv6 but v6 is manually validated).
CVE-2024-42154 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.5 USE OF UNINITIALIZED VARIABLE CWE-457
In the Linux kernel, the following vulnerability has been resolved: bpf: Avoid uninitialized value in BPF_CORE_READ_BITFIELD.
CVE-2024-42161 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
Siemens reported these vulnerabilities to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

Only build and run applications from trusted sources
Currently no fix is available

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-503939 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:

Do not click web links or open attachments in unsolicited email messages.
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.
5. UPDATE HISTORY

March 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 7.8
  • ATTENTION: Low attack complexity
  • Vendor: Siemens
  • Equipment: SIMATIC S7-1500 TM MFP
  • Vulnerabilities: Double Free, Use After Free, NULL Pointer Dereference, Buffer Access with Incorrect Length Value, Use of Uninitialized Variable

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to execute arbitrary code, cause a denial-of-service condition, or gain unauthorized access to sensitive information.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • SIMATIC S7-1500 TM MFP – BIOS: All versions

3.2 VULNERABILITY OVERVIEW

3.2.1 DOUBLE FREE CWE-415

In the Linux kernel, the following vulnerability has been resolved: net: ethernet: lantiq_etop: fix double free in detach. The number of the currently released descriptor is never incremented, which results in the same skb being released multiple times.

CVE-2024-41046 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.2 USE AFTER FREE CWE-416

In the Linux kernel, the following vulnerability has been resolved: filelock: fix potential use-after-free in posix_lock_inode Light Hsieh reported a KASAN UAF warning in trace_posix_lock_inode(). The request pointer had been changed earlier to point to a lock entry that was added to the inode’s list. However, before the tracepoint could fire, another task raced in and freed that lock. Fix this by moving the tracepoint inside the spinlock, which should ensure that this doesn’t happen.

CVE-2024-41049 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.3 NULL POINTER DEREFERENCE CWE-476

In the Linux kernel, the following vulnerability has been resolved: mm: prevent derefencing NULL ptr in pfn_section_valid() Commit 5ec8e8ea8b77 (“mm/sparsemem: fix race in accessing memory_section->usage”) changed pfn_section_valid() to add a READ_ONCE() call around “ms->usage” to fix a race with section_deactivate() where ms->usage can be cleared. The READ_ONCE() call, by itself, is not enough to prevent NULL pointer dereference. We need to check its value before dereferencing it.

CVE-2024-41055 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.4 BUFFER ACCESS WITH INCORRECT LENGTH VALUE CWE-805

In the Linux kernel, the following vulnerability has been resolved: tcp_metrics: validate source addr length I don’t see anything checking that TCP_METRICS_ATTR_SADDR_IPV4 is at least 4 bytes long, and the policy doesn’t have an entry for this attribute at all (neither does it for IPv6 but v6 is manually validated).

CVE-2024-42154 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.5 USE OF UNINITIALIZED VARIABLE CWE-457

In the Linux kernel, the following vulnerability has been resolved: bpf: Avoid uninitialized value in BPF_CORE_READ_BITFIELD.

CVE-2024-42161 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • Only build and run applications from trusted sources
  • Currently no fix is available

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-503939 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.

5. UPDATE HISTORY

  • March 13, 2025: Initial Publication

 Read More

Siemens SCALANCE M-800 and SC-600 Families

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 6.3
ATTENTION: Exploitable remotely
Vendor: Siemens
Equipment: SCALANCE M-800 family (incl. S615, MUM-800 and RM1224), SCALANCE SC-600 family
Vulnerability: Partial String Comparison

2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker to obtain partial invalid usernames accepted by the server. A remote attacker would need access to a valid certificate in order to perform a successful attack.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:

Siemens SCALANCE SC-600 family: All versions
Siemens RUGGEDCOM RM1224 LTE(4G) EU (6GK6108-4AM00-2BA2): All versions prior to V8.2.1
Siemens SCALANCE M876-3 (6GK5876-3AA02-2BA2): vers: All versions prior to V8.2.1
Siemens SCALANCE M876-3 (ROK) (6GK5876-3AA02-2EA2): All versions prior to V8.2.1
Siemens SCALANCE M876-4 (6GK5876-4AA10-2BA2): All versions prior to V8.2.1
Siemens SCALANCE M876-4 (EU) (6GK5876-4AA00-2BA2): All versions prior to V8.2.1
Siemens SCALANCE M876-4 (NAM) (6GK5876-4AA00-2DA2): All versions prior to V8.2.1
Siemens SCALANCE MUB852-1 (A1) (6GK5852-1EA10-1AA1): All versions prior to V8.2.1
Siemens SCALANCE MUB852-1 (B1) (6GK5852-1EA10-1BA1): All versions prior to V8.2.1
Siemens SCALANCE MUM853-1 (A1) (6GK5853-2EA10-2AA1): All versions prior to V8.2.1
Siemens SCALANCE MUM853-1 (B1) (6GK5853-2EA10-2BA1): All versions prior to V8.2.1
Siemens SCALANCE MUM853-1 (EU) (6GK5853-2EA00-2DA1): All versions prior to V8.2.1
Siemens RUGGEDCOM RM1224 LTE(4G) NAM (6GK6108-4AM00-2DA2): All versions prior to V8.2.1
Siemens SCALANCE MUM856-1 (A1) (6GK5856-2EA10-3AA1): All versions prior to V8.2.1
Siemens SCALANCE MUM856-1 (B1) (6GK5856-2EA10-3BA1): All versions prior to V8.2.1
Siemens SCALANCE MUM856-1 (CN) (6GK5856-2EA00-3FA1): All versions prior to V8.2.1
Siemens SCALANCE MUM856-1 (EU) (6GK5856-2EA00-3DA1): All versions prior to V8.2.1
Siemens SCALANCE MUM856-1 (RoW) (6GK5856-2EA00-3AA1): All versions prior to V8.2.1
Siemens SCALANCE S615 EEC LAN-Router (6GK5615-0AA01-2AA2): All versions prior to V8.2.1
Siemens SCALANCE S615 LAN-Router (6GK5615-0AA00-2AA2): All versions prior to V8.2.1
Siemens SCALANCE M804PB (6GK5804-0AP00-2AA2): All versions prior to V8.2.1
Siemens SCALANCE M812-1 ADSL-Router family: All versions prior to V8.2.1
Siemens SCALANCE M816-1 ADSL-Router family: All versions prior to V8.2.1
Siemens SCALANCE M826-2 SHDSL-Router (6GK5826-2AB00-2AB2): All versions prior to V8.2.1
Siemens SCALANCE M874-2 (6GK5874-2AA00-2AA2): All versions prior to V8.2.1
Siemens SCALANCE M874-3 3G-Router (CN) (6GK5874-3AA00-2FA2): All versions prior to V8.2.1
Siemens SCALANCE M874-3 (6GK5874-3AA00-2AA2): All versions prior to V8.2.1

3.2 VULNERABILITY OVERVIEW
3.2.1 PARTIAL STRING COMPARISON CWE-187
Affected devices improperly validate usernames during OpenVPN authentication. This could allow an attacker to get partial invalid usernames accepted by the server.
CVE-2025-23384 has been assigned to this vulnerability. A CVSS v3 base score of 3.7 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:L/A:N).
A CVSS v4 score has also been calculated for CVE-2025-23384. A base score of 6.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:N/VI:L/VA:N/SC:N/SI:N/SA:N).
3.4 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.5 RESEARCHER
Siemens reported this vulnerability to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

SCALANCE SC-600 family: Currently no fix is available.
RUGGEDCOM RM1224 LTE(4G) EU (6GK6108-4AM00-2BA2), RUGGEDCOM RM1224 LTE(4G) NAM (6GK6108-4AM00-2DA2), SCALANCE M804PB (6GK5804-0AP00-2AA2), SCALANCE M812-1 ADSL-Router family, SCALANCE M816-1 ADSL-Router family, SCALANCE M826-2 SHDSL-Router (6GK5826-2AB00-2AB2), SCALANCE M874-2 (6GK5874-2AA00-2AA2), SCALANCE M874-3 (6GK5874-3AA00-2AA2), SCALANCE M874-3 3G-Router (CN) (6GK5874-3AA00-2FA2), SCALANCE M876-3 (6GK5876-3AA02-2BA2), SCALANCE M876-3 (ROK) (6GK5876-3AA02-2EA2), SCALANCE M876-4 (6GK5876-4AA10-2BA2), SCALANCE M876-4 (EU) (6GK5876-4AA00-2BA2), SCALANCE M876-4 (NAM) (6GK5876-4AA00-2DA2), SCALANCE MUB852-1 (A1) (6GK5852-1EA10-1AA1), SCALANCE MUB852-1 (B1) (6GK5852-1EA10-1BA1), SCALANCE MUM853-1 (A1) (6GK5853-2EA10-2AA1), SCALANCE MUM853-1 (B1) (6GK5853-2EA10-2BA1), SCALANCE MUM853-1 (EU) (6GK5853-2EA00-2DA1), SCALANCE MUM856-1 (A1) (6GK5856-2EA10-3AA1), SCALANCE MUM856-1 (B1) (6GK5856-2EA10-3BA1), SCALANCE MUM856-1 (CN) (6GK5856-2EA00-3FA1), SCALANCE MUM856-1 (EU) (6GK5856-2EA00-3DA1), SCALANCE MUM856-1 (RoW) (6GK5856-2EA00-3AA1), SCALANCE S615 EEC LAN-Router (6GK5615-0AA01-2AA2), SCALANCE S615 LAN-Router (6GK5615-0AA00-2AA2): Update to V8.2.1 or later version.
All affected products: Apply a strong password policy for your devices.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-280834 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:

Do not click web links or open attachments in unsolicited email messages.
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability has a high attack complexity.
5. UPDATE HISTORY

March 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 6.3
  • ATTENTION: Exploitable remotely
  • Vendor: Siemens
  • Equipment: SCALANCE M-800 family (incl. S615, MUM-800 and RM1224), SCALANCE SC-600 family
  • Vulnerability: Partial String Comparison

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to obtain partial invalid usernames accepted by the server. A remote attacker would need access to a valid certificate in order to perform a successful attack.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • Siemens SCALANCE SC-600 family: All versions
  • Siemens RUGGEDCOM RM1224 LTE(4G) EU (6GK6108-4AM00-2BA2): All versions prior to V8.2.1
  • Siemens SCALANCE M876-3 (6GK5876-3AA02-2BA2): vers: All versions prior to V8.2.1
  • Siemens SCALANCE M876-3 (ROK) (6GK5876-3AA02-2EA2): All versions prior to V8.2.1
  • Siemens SCALANCE M876-4 (6GK5876-4AA10-2BA2): All versions prior to V8.2.1
  • Siemens SCALANCE M876-4 (EU) (6GK5876-4AA00-2BA2): All versions prior to V8.2.1
  • Siemens SCALANCE M876-4 (NAM) (6GK5876-4AA00-2DA2): All versions prior to V8.2.1
  • Siemens SCALANCE MUB852-1 (A1) (6GK5852-1EA10-1AA1): All versions prior to V8.2.1
  • Siemens SCALANCE MUB852-1 (B1) (6GK5852-1EA10-1BA1): All versions prior to V8.2.1
  • Siemens SCALANCE MUM853-1 (A1) (6GK5853-2EA10-2AA1): All versions prior to V8.2.1
  • Siemens SCALANCE MUM853-1 (B1) (6GK5853-2EA10-2BA1): All versions prior to V8.2.1
  • Siemens SCALANCE MUM853-1 (EU) (6GK5853-2EA00-2DA1): All versions prior to V8.2.1
  • Siemens RUGGEDCOM RM1224 LTE(4G) NAM (6GK6108-4AM00-2DA2): All versions prior to V8.2.1
  • Siemens SCALANCE MUM856-1 (A1) (6GK5856-2EA10-3AA1): All versions prior to V8.2.1
  • Siemens SCALANCE MUM856-1 (B1) (6GK5856-2EA10-3BA1): All versions prior to V8.2.1
  • Siemens SCALANCE MUM856-1 (CN) (6GK5856-2EA00-3FA1): All versions prior to V8.2.1
  • Siemens SCALANCE MUM856-1 (EU) (6GK5856-2EA00-3DA1): All versions prior to V8.2.1
  • Siemens SCALANCE MUM856-1 (RoW) (6GK5856-2EA00-3AA1): All versions prior to V8.2.1
  • Siemens SCALANCE S615 EEC LAN-Router (6GK5615-0AA01-2AA2): All versions prior to V8.2.1
  • Siemens SCALANCE S615 LAN-Router (6GK5615-0AA00-2AA2): All versions prior to V8.2.1
  • Siemens SCALANCE M804PB (6GK5804-0AP00-2AA2): All versions prior to V8.2.1
  • Siemens SCALANCE M812-1 ADSL-Router family: All versions prior to V8.2.1
  • Siemens SCALANCE M816-1 ADSL-Router family: All versions prior to V8.2.1
  • Siemens SCALANCE M826-2 SHDSL-Router (6GK5826-2AB00-2AB2): All versions prior to V8.2.1
  • Siemens SCALANCE M874-2 (6GK5874-2AA00-2AA2): All versions prior to V8.2.1
  • Siemens SCALANCE M874-3 3G-Router (CN) (6GK5874-3AA00-2FA2): All versions prior to V8.2.1
  • Siemens SCALANCE M874-3 (6GK5874-3AA00-2AA2): All versions prior to V8.2.1

3.2 VULNERABILITY OVERVIEW

3.2.1 PARTIAL STRING COMPARISON CWE-187

Affected devices improperly validate usernames during OpenVPN authentication. This could allow an attacker to get partial invalid usernames accepted by the server.

CVE-2025-23384 has been assigned to this vulnerability. A CVSS v3 base score of 3.7 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:L/A:N).

A CVSS v4 score has also been calculated for CVE-2025-23384. A base score of 6.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:N/VI:L/VA:N/SC:N/SI:N/SA:N).

3.4 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.5 RESEARCHER

Siemens reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • SCALANCE SC-600 family: Currently no fix is available.
  • RUGGEDCOM RM1224 LTE(4G) EU (6GK6108-4AM00-2BA2), RUGGEDCOM RM1224 LTE(4G) NAM (6GK6108-4AM00-2DA2), SCALANCE M804PB (6GK5804-0AP00-2AA2), SCALANCE M812-1 ADSL-Router family, SCALANCE M816-1 ADSL-Router family, SCALANCE M826-2 SHDSL-Router (6GK5826-2AB00-2AB2), SCALANCE M874-2 (6GK5874-2AA00-2AA2), SCALANCE M874-3 (6GK5874-3AA00-2AA2), SCALANCE M874-3 3G-Router (CN) (6GK5874-3AA00-2FA2), SCALANCE M876-3 (6GK5876-3AA02-2BA2), SCALANCE M876-3 (ROK) (6GK5876-3AA02-2EA2), SCALANCE M876-4 (6GK5876-4AA10-2BA2), SCALANCE M876-4 (EU) (6GK5876-4AA00-2BA2), SCALANCE M876-4 (NAM) (6GK5876-4AA00-2DA2), SCALANCE MUB852-1 (A1) (6GK5852-1EA10-1AA1), SCALANCE MUB852-1 (B1) (6GK5852-1EA10-1BA1), SCALANCE MUM853-1 (A1) (6GK5853-2EA10-2AA1), SCALANCE MUM853-1 (B1) (6GK5853-2EA10-2BA1), SCALANCE MUM853-1 (EU) (6GK5853-2EA00-2DA1), SCALANCE MUM856-1 (A1) (6GK5856-2EA10-3AA1), SCALANCE MUM856-1 (B1) (6GK5856-2EA10-3BA1), SCALANCE MUM856-1 (CN) (6GK5856-2EA00-3FA1), SCALANCE MUM856-1 (EU) (6GK5856-2EA00-3DA1), SCALANCE MUM856-1 (RoW) (6GK5856-2EA00-3AA1), SCALANCE S615 EEC LAN-Router (6GK5615-0AA01-2AA2), SCALANCE S615 LAN-Router (6GK5615-0AA00-2AA2): Update to V8.2.1 or later version.
  • All affected products: Apply a strong password policy for your devices.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-280834 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability has a high attack complexity.

5. UPDATE HISTORY

  • March 13, 2025: Initial Publication

 Read More

Siemens SINAMICS S200

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 9.5
ATTENTION: Exploitable remotely/low attack complexity
Vendor: Siemens
Equipment: SINAMICS S200
Vulnerability: Improper Authentication

2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker to download untrusted firmware that could damage or compromise the device.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:

Siemens SINAMICS S200: All versions

3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER AUTHENTICATION CWE-287
The affected device contains an unlocked bootloader. This security oversight enables attackers to inject malicious code or to install untrusted firmware. The intrinsic security features designed to protect against data manipulation and unauthorized access are compromised when the bootloader is not secured.
CVE-2024-56336 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-56336. A base score of 9.5 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
Siemens reported this vulnerability to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

SINAMICS S200: Follow the general security recommendations and apply defense in depth. Contact your local customer service for further support

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-787280 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:

Do not click web links or open attachments in unsolicited email messages.
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.
5. UPDATE HISTORY

March 13, 2025: Initial Publication

  

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.5
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SINAMICS S200
  • Vulnerability: Improper Authentication

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to download untrusted firmware that could damage or compromise the device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • Siemens SINAMICS S200: All versions

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER AUTHENTICATION CWE-287

The affected device contains an unlocked bootloader. This security oversight enables attackers to inject malicious code or to install untrusted firmware. The intrinsic security features designed to protect against data manipulation and unauthorized access are compromised when the bootloader is not secured.

CVE-2024-56336 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-56336. A base score of 9.5 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • SINAMICS S200: Follow the general security recommendations and apply defense in depth. Contact your local customer service for further support

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-787280 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • March 13, 2025: Initial Publication

 

 Read More

Siemens Teamcenter Visualization and Tecnomatrix Plant Simulation

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 7.3
ATTENTION: Low attack complexity
Vendor: Siemens
Equipment: Teamcenter Visualization and Tecnomatrix Plant Simulation
Vulnerabilities: Out-of-bounds Write, Improper Restriction of Operations within the Bounds of a Memory Buffer, Out-of-bounds Read, Use After Free

2. RISK EVALUATION
Successful exploitation of these vulnerabilities could cause the application to crash or potentially lead to arbitrary code execution.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports the following products are affected:

Teamcenter Visualization V14.3: Versions prior to V14.3.0.13
Teamcenter Visualization V2312: Versions prior to V2312.0009
Teamcenter Visualization V2406: Versions prior to V2406.0007
Teamcenter Visualization V2412: Versions prior to V2412.0002
Tecnomatix Plant Simulation V2302: Versions prior to V2302.0021
Tecnomatix Plant Simulation V2404: Versions prior to V2404.0010

3.2 VULNERABILITY OVERVIEW
3.2.1 OUT-OF-BOUNDS WRITE CWE-787
The affected applications contain an out-of-bounds write vulnerability when parsing a specially crafted WRL file. This could allow an attacker to execute code in the context of the current process.
CVE-2025-23396 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-23396. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.2 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119
The affected application is vulnerable to memory corruption while parsing specially crafted WRL files. This could allow an attacker to execute code in the context of the current process.
CVE-2025-23397 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-23397. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.3 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119
The affected application is vulnerable to memory corruption while parsing specially crafted WRL files. This could allow an attacker to execute code in the context of the current process.
CVE-2025-23398 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-23398. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.4 OUT-OF-BOUNDS READ CWE-125
The affected applications contain an out of bounds read past the end of an allocated structure while parsing specially crafted WRL files. This could allow an attacker to execute code in the context of the current process.
CVE-2025-23399 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-23399. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.5 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119
The affected application is vulnerable to memory corruption while parsing specially crafted WRL files. This could allow an attacker to execute code in the context of the current process.
CVE-2025-23400 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-23400. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.6 OUT-OF-BOUNDS READ CWE-125
The affected applications contain an out of bounds read past the end of an allocated structure while parsing specially crafted WRL files. This could allow an attacker to execute code in the context of the current process.
CVE-2025-23401 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-23401. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.7 USE AFTER FREE CWE-416
The affected applications contain a use-after-free vulnerability that could be triggered while parsing specially crafted WRL files. An attacker could leverage this vulnerability to execute code in the context of the current process.
CVE-2025-23402 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-23402. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.8 OUT-OF-BOUNDS READ CWE-125
The affected applications contain an out-of-bounds read past the end of an allocated structure while parsing specially crafted WRL files. This could allow an attacker to execute code in the context of the current process.
CVE-2025-27438 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-27438. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
Jin Huang from ADLab of Venustech and Michael Heinzl reported these vulnerabilities to Siemens.
4. MITIGATIONS
Siemens has released new versions for the affected products and recommends to update to the latest versions:

Teamcenter Visualization V14.3: Update to V14.3.0.13 or later version.
Teamcenter Visualization V2312: Update to V2312.0009 or later version.
Teamcenter Visualization V2406: Update to V2406.0007 or later version.
Teamcenter Visualization V2412: Update to V2412.0002 or later version.
Tecnomatix Plant Simulation V2302: Update to V2302.0021 or later version.
Tecnomatix Plant Simulation V2404: Update to V2404.0010 or later version.

To reduce risk, Siemens recommends that users not open untrusted WRL files in affected applications.
As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-050438 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:

Do not click web links or open attachments in unsolicited email messages.
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.
5. UPDATE HISTORY

March 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.3
  • ATTENTION: Low attack complexity
  • Vendor: Siemens
  • Equipment: Teamcenter Visualization and Tecnomatrix Plant Simulation
  • Vulnerabilities: Out-of-bounds Write, Improper Restriction of Operations within the Bounds of a Memory Buffer, Out-of-bounds Read, Use After Free

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could cause the application to crash or potentially lead to arbitrary code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports the following products are affected:

  • Teamcenter Visualization V14.3: Versions prior to V14.3.0.13
  • Teamcenter Visualization V2312: Versions prior to V2312.0009
  • Teamcenter Visualization V2406: Versions prior to V2406.0007
  • Teamcenter Visualization V2412: Versions prior to V2412.0002
  • Tecnomatix Plant Simulation V2302: Versions prior to V2302.0021
  • Tecnomatix Plant Simulation V2404: Versions prior to V2404.0010

3.2 VULNERABILITY OVERVIEW

3.2.1 OUT-OF-BOUNDS WRITE CWE-787

The affected applications contain an out-of-bounds write vulnerability when parsing a specially crafted WRL file. This could allow an attacker to execute code in the context of the current process.

CVE-2025-23396 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-23396. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

The affected application is vulnerable to memory corruption while parsing specially crafted WRL files. This could allow an attacker to execute code in the context of the current process.

CVE-2025-23397 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-23397. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.3 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

The affected application is vulnerable to memory corruption while parsing specially crafted WRL files. This could allow an attacker to execute code in the context of the current process.

CVE-2025-23398 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-23398. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.4 OUT-OF-BOUNDS READ CWE-125

The affected applications contain an out of bounds read past the end of an allocated structure while parsing specially crafted WRL files. This could allow an attacker to execute code in the context of the current process.

CVE-2025-23399 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-23399. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.5 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

The affected application is vulnerable to memory corruption while parsing specially crafted WRL files. This could allow an attacker to execute code in the context of the current process.

CVE-2025-23400 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-23400. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.6 OUT-OF-BOUNDS READ CWE-125

The affected applications contain an out of bounds read past the end of an allocated structure while parsing specially crafted WRL files. This could allow an attacker to execute code in the context of the current process.

CVE-2025-23401 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-23401. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.7 USE AFTER FREE CWE-416

The affected applications contain a use-after-free vulnerability that could be triggered while parsing specially crafted WRL files. An attacker could leverage this vulnerability to execute code in the context of the current process.

CVE-2025-23402 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-23402. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.8 OUT-OF-BOUNDS READ CWE-125

The affected applications contain an out-of-bounds read past the end of an allocated structure while parsing specially crafted WRL files. This could allow an attacker to execute code in the context of the current process.

CVE-2025-27438 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-27438. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Jin Huang from ADLab of Venustech and Michael Heinzl reported these vulnerabilities to Siemens.

4. MITIGATIONS

Siemens has released new versions for the affected products and recommends to update to the latest versions:

To reduce risk, Siemens recommends that users not open untrusted WRL files in affected applications.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-050438 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.

5. UPDATE HISTORY

  • March 13, 2025: Initial Publication

 Read More

Siemens OPC UA

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 9.3
ATTENTION: Exploitable remotely/low attack complexity
Vendor: Siemens
Equipment: OPC UA
Vulnerabilities: Observable Timing Discrepancy, Authentication Bypass by Primary Weakness

2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to bypass application authentication and gain access to the data managed by the server.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:

Industrial Edge for Machine Tools (formerly known as “SINUMERIK Edge”): All versions (CVE-2024-42513)
SIMIT V11: All versions (CVE-2024-42512)
SIMATIC BRAUMAT: All versions from V8.0 SP1 up to but not including V8.1 (CVE-2024-42513)
SIMATIC Energy Manager PRO: All versions from V7.5 up to but not including V7.5 Update 2
SIMATIC Energy Manager PRO: All versions after V7.2 Update 6
SIMATIC IPC DiagMonitor: All versions (CVE-2024-42513)
SIMATIC SISTAR: All versions from V8.0 SP1 up to but not including V8.1 (CVE-2024-42513)
SIMATIC WinCC Unified V18: All versions (CVE-2024-42513)
SIMATIC WinCC Unified V19: All versions before V19 Update 4 (CVE-2024-42513)
SIMATIC WinCC V8.0: All versions before V8.0 Update 3 (CVE-2024-42513)

3.2 VULNERABILITY OVERVIEW
3.2.1 OBSERVABLE TIMING DISCREPANCY CWE-208
Vulnerability in the OPC UA .NET standard stack before 1.5.374.158 allows an unauthorized attacker to bypass application authentication when the deprecated Basic128Rsa15 security policy is enabled.
CVE-2024-42512 has been assigned to this vulnerability. A CVSS v3 base score of 7.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:N).
A CVSS v4 score has also been calculated for CVE-2024-42512. A base score of 9.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:H/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N).
3.2.2 AUTHENTICATION BYPASS BY PRIMARY WEAKNESS CWE-305
Vulnerability in the OPC UA .NET standard stack before 1.5.374.158 allows an unauthorized attacker to bypass application authentication when using HTTPS endpoints.
CVE-2024-42513 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N).
A CVSS v4 score has also been calculated for CVE-2024-42513. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
Siemens reported these vulnerabilities to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

SIMATIC Energy Manager PRO: Update to V7.5 Update 2 or later version.
(CVE-2024-42512) SIMATIC Energy Manager PRO, SIMIT V11: Currently no fix is available.
(CVE-2024-42513) SIMATIC WinCC Unified V18, SIMATIC WinCC Unified V19: Please note that the affected functionality (HTTPS endpoint in OPC UA server) is deactivated by default in Unified RT. Systems running with default configuration are therefore not affected by this vulnerability.
(CVE-2024-42513) SIMATIC IPC DiagMonitor: Please note that the affected functionality (HTTPS endpoint in OPC UA Server) is deactivated by default. Systems running with default configuration are therefore not affected by this vulnerability.
(CVE-2024-42513) Industrial Edge for Machine Tools (formerly known as “SINUMERIK Edge”), SIMATIC IPC DiagMonitor: Currently no fix is planned.
(CVE-2024-42513) SIMATIC Energy Manager PRO, SIMATIC WinCC Unified V18: Currently no fix is available.
(CVE-2024-42513) SIMATIC WinCC Unified V19: Update to V19 Update 4 or later version.
(CVE-2024-42513) SIMATIC WinCC V8.0: Update to V8.0 Update 3 or later version.
(CVE-2024-42513) SIMATIC BRAUMAT, SIMATIC SISTAR: Update to V8.1 or later version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-858251 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY

March 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: OPC UA
  • Vulnerabilities: Observable Timing Discrepancy, Authentication Bypass by Primary Weakness

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to bypass application authentication and gain access to the data managed by the server.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • Industrial Edge for Machine Tools (formerly known as “SINUMERIK Edge”): All versions (CVE-2024-42513)
  • SIMIT V11: All versions (CVE-2024-42512)
  • SIMATIC BRAUMAT: All versions from V8.0 SP1 up to but not including V8.1 (CVE-2024-42513)
  • SIMATIC Energy Manager PRO: All versions from V7.5 up to but not including V7.5 Update 2
  • SIMATIC Energy Manager PRO: All versions after V7.2 Update 6
  • SIMATIC IPC DiagMonitor: All versions (CVE-2024-42513)
  • SIMATIC SISTAR: All versions from V8.0 SP1 up to but not including V8.1 (CVE-2024-42513)
  • SIMATIC WinCC Unified V18: All versions (CVE-2024-42513)
  • SIMATIC WinCC Unified V19: All versions before V19 Update 4 (CVE-2024-42513)
  • SIMATIC WinCC V8.0: All versions before V8.0 Update 3 (CVE-2024-42513)

3.2 VULNERABILITY OVERVIEW

3.2.1 OBSERVABLE TIMING DISCREPANCY CWE-208

Vulnerability in the OPC UA .NET standard stack before 1.5.374.158 allows an unauthorized attacker to bypass application authentication when the deprecated Basic128Rsa15 security policy is enabled.

CVE-2024-42512 has been assigned to this vulnerability. A CVSS v3 base score of 7.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2024-42512. A base score of 9.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:H/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N).

3.2.2 AUTHENTICATION BYPASS BY PRIMARY WEAKNESS CWE-305

Vulnerability in the OPC UA .NET standard stack before 1.5.374.158 allows an unauthorized attacker to bypass application authentication when using HTTPS endpoints.

CVE-2024-42513 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2024-42513. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • SIMATIC Energy Manager PRO: Update to V7.5 Update 2 or later version.
  • (CVE-2024-42512) SIMATIC Energy Manager PRO, SIMIT V11: Currently no fix is available.
  • (CVE-2024-42513) SIMATIC WinCC Unified V18, SIMATIC WinCC Unified V19: Please note that the affected functionality (HTTPS endpoint in OPC UA server) is deactivated by default in Unified RT. Systems running with default configuration are therefore not affected by this vulnerability.
  • (CVE-2024-42513) SIMATIC IPC DiagMonitor: Please note that the affected functionality (HTTPS endpoint in OPC UA Server) is deactivated by default. Systems running with default configuration are therefore not affected by this vulnerability.
  • (CVE-2024-42513) Industrial Edge for Machine Tools (formerly known as “SINUMERIK Edge”), SIMATIC IPC DiagMonitor: Currently no fix is planned.
  • (CVE-2024-42513) SIMATIC Energy Manager PRO, SIMATIC WinCC Unified V18: Currently no fix is available.
  • (CVE-2024-42513) SIMATIC WinCC Unified V19: Update to V19 Update 4 or later version.
  • (CVE-2024-42513) SIMATIC WinCC V8.0: Update to V8.0 Update 3 or later version.
  • (CVE-2024-42513) SIMATIC BRAUMAT, SIMATIC SISTAR: Update to V8.1 or later version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-858251 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • March 13, 2025: Initial Publication

 Read More

CISA Adds Two Known Exploited Vulnerabilities to Catalog

 ​CISA has added two new vulnerabilities to its Known Exploited Vulnerabilities Catalog, based on evidence of active exploitation.

CVE-2025-24201 Apple Multiple Products WebKit Out-of-Bounds Write Vulnerability
CVE-2025-21590 Juniper Junos OS Improper Isolation or Compartmentalization Vulnerability

These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise.
Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the Known Exploited Vulnerabilities Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information.
Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria. 

CISA has added two new vulnerabilities to its Known Exploited Vulnerabilities Catalog, based on evidence of active exploitation.

  • CVE-2025-24201 Apple Multiple Products WebKit Out-of-Bounds Write Vulnerability
  • CVE-2025-21590 Juniper Junos OS Improper Isolation or Compartmentalization Vulnerability

These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise.

Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the Known Exploited Vulnerabilities Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information.

Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.

 Read More

Scroll to Top