Siemens RUGGEDCOM APE1808 Devices

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v3 7.5
ATTENTION: Exploitable remotely/low attack complexity
Vendor: Siemens
Equipment: RUGGEDCOM APE1808 Devices
Vulnerabilities: Out-of-bounds Read, Insertion of Sensitive Information Into Sent Data, Allocation of Resources Without Limits or Throttling, Integer Overflow or Wraparound, Path Traversal, Out-of-bounds Write, HTTP Request/Response Splitting

2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to cause a denial-of service condition, perform a machine-in-the middle attack (MITM), escalate privileges, execute unauthorized code, and access unauthorized systems and information.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:

Siemens RUGGEDCOM APE1808: All versions

3.2 VULNERABILITY OVERVIEW
3.2.1 OUT-OF-BOUNDS READ CWE-125
An out-of-bounds read vulnerability [CWE-125] in FortiOS SSLVPN web portal versions 7.4.0 through 7.4.4, versions 7.2.0 through 7.2.8, 7.0 all versions, and 6.4 all versions may allow an authenticated attacker to perform a denial-of-service on the SSLVPN web portal via a specially crafted URL.
CVE-2024-36504 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.2 INSERTION OF SENSITIVE INFORMATION INTO SENT DATA CWE-201
An insertion of sensitive information into sent data vulnerability [CWE-201] in FortiOS 7.6.0, 7.4.0 through 7.4.4 may allow an attacker in a man-in-the-middle position to retrieve the RADIUS accounting server shared secret via intercepting accounting-requests.
CVE-2024-46665 has been assigned to this vulnerability. A CVSS v3 base score of 3.7 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:N).
3.2.3 ALLOCATION OF RESOURCES WITHOUT LIMITS OR THROTTLING CWE-770
An allocation of resources without limits or throttling [CWE-770] vulnerability in FortiOS versions 7.6.0, versions 7.4.4 through 7.4.0, 7.2 all versions, 7.0 all versions, 6.4 all versions may allow a remote unauthenticated attacker to prevent access to the GUI via specially crafted requests directed at specific endpoints.
CVE-2024-46666 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).
3.2.4 ALLOCATION OF RESOURCES WITHOUT LIMITS OR THROTTLING CWE-770
An allocation of resources without limits or throttling vulnerability [CWE-770] in FortiOS versions 7.4.0 through 7.4.4, versions 7.2.0 through 7.2.8, versions 7.0.0 through 7.0.15, and versions 6.4.0 through 6.4.15 may allow an unauthenticated remote user to consume all system memory via multiple large file uploads.
CVE-2024-46668 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
3.2.5 INTEGER OVERFLOW OR WRAPAROUND CWE-190
An Integer Overflow or Wraparound vulnerability in version 7.4.4 and below, version 7.2.10 and below; FortiSASE version 23.4.b FortiOS tenant IPsec IKE service may allow an authenticated attacker to crash the IPsec tunnel via crafted requests, resulting in potential denial-of-service.
CVE-2024-46669 has been assigned to this vulnerability. A CVSS v3 base score of 3.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:A/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:L).
3.2.6 OUT-OF-BOUNDS READ CWE-125
An Out-of-bounds Read vulnerability in FortiOS version 7.6.0, version 7.4.4 and below, version 7.2.9 and below and FortiSASE FortiOS tenant version 24.3.b IPsec IKE service may allow an unauthenticated remote attacker to trigger memory consumption leading to denial-of-service via crafted requests.
CVE-2024-46670 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
3.2.7 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22
A improper limitation of a pathname to a restricted directory (‘path traversal’) in Fortinet FortiManager versions 7.6.0 through 7.6.1, 7.4.1 through 7.4.3, FortiOS versions 7.6.0, 7.4.0 through 7.4.4, 7.2.5 through 7.2.9, 7.0.0 through 7.0.15, 6.4.0 through 6.4.15, FortiProxy 7.4.0 through 7.4.5, 7.2.0 through 7.2.11, 7.0.0 through 7.0.18, 2.0.0 through 2.0.14, 1.2.0 through 1.2.13, 1.1.0 through 1.1.6, 1.0.0 through 1.0.7, FortiManager Cloud versions 7.4.1 through 7.4.3 allows attacker to trigger an escalation of privilege via specially crafted packets.
CVE-2024-48884 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
3.2.8 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22
A improper limitation of a pathname to a restricted directory (‘path traversal’) in Fortinet FortiRecorder versions 7.2.0 through 7.2.1, 7.0.0 through 7.0.4, FortiWeb versions 7.6.0, 7.4.0 through 7.4.4, 7.2.0 through 7.2.10, 7.0.0 through 7.0.10, 6.4.0 through 6.4.3, FortiVoice versions 7.0.0 through 7.0.4, 6.4.0 through 6.4.9, 6.0.0 through 6.0.12 allows attacker to escalate privilege via specially crafted packets.
CVE-2024-48885 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:N/I:N/A:H).
3.2.9 OUT-OF-BOUNDS WRITE CWE-787
A out-of-bounds write in Fortinet FortiOS versions 7.6.0, 7.4.0 through 7.4.6, 7.2.0 through 7.2.10, 7.0.0 through 7.0.16, 6.4.0 through 6.4.15 allows attacker to trigger a denial-of-service via specially crafted packets.
CVE-2024-52963 has been assigned to this vulnerability. A CVSS v3 base score of 3.7 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:L).
3.2.10 IMPROPER NEUTRALIZATION OF CRLF SEQUENCES IN HTTP HEADERS (‘HTTP REQUEST/RESPONSE SPLITTING’) CWE-113
An improper neutralization of crlf sequences in http headers (‘http response splitting’) in Fortinet FortiOS 7.2.0 through 7.6.0, FortiProxy 7.2.0 through 7.4.5 allows attacker to execute unauthorized code or commands via crafted HTTP header.
CVE-2024-54021 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
Siemens reported these vulnerabilities to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

RUGGEDCOM APE1808: Contact customer support to receive patch and update information.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-770770 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:

Do not click web links or open attachments in unsolicited email messages.
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY

February 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 7.5
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: RUGGEDCOM APE1808 Devices
  • Vulnerabilities: Out-of-bounds Read, Insertion of Sensitive Information Into Sent Data, Allocation of Resources Without Limits or Throttling, Integer Overflow or Wraparound, Path Traversal, Out-of-bounds Write, HTTP Request/Response Splitting

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to cause a denial-of service condition, perform a machine-in-the middle attack (MITM), escalate privileges, execute unauthorized code, and access unauthorized systems and information.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • Siemens RUGGEDCOM APE1808: All versions

3.2 VULNERABILITY OVERVIEW

3.2.1 OUT-OF-BOUNDS READ CWE-125

An out-of-bounds read vulnerability [CWE-125] in FortiOS SSLVPN web portal versions 7.4.0 through 7.4.4, versions 7.2.0 through 7.2.8, 7.0 all versions, and 6.4 all versions may allow an authenticated attacker to perform a denial-of-service on the SSLVPN web portal via a specially crafted URL.

CVE-2024-36504 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.2 INSERTION OF SENSITIVE INFORMATION INTO SENT DATA CWE-201

An insertion of sensitive information into sent data vulnerability [CWE-201] in FortiOS 7.6.0, 7.4.0 through 7.4.4 may allow an attacker in a man-in-the-middle position to retrieve the RADIUS accounting server shared secret via intercepting accounting-requests.

CVE-2024-46665 has been assigned to this vulnerability. A CVSS v3 base score of 3.7 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:N/A:N).

3.2.3 ALLOCATION OF RESOURCES WITHOUT LIMITS OR THROTTLING CWE-770

An allocation of resources without limits or throttling [CWE-770] vulnerability in FortiOS versions 7.6.0, versions 7.4.4 through 7.4.0, 7.2 all versions, 7.0 all versions, 6.4 all versions may allow a remote unauthenticated attacker to prevent access to the GUI via specially crafted requests directed at specific endpoints.

CVE-2024-46666 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).

3.2.4 ALLOCATION OF RESOURCES WITHOUT LIMITS OR THROTTLING CWE-770

An allocation of resources without limits or throttling vulnerability [CWE-770] in FortiOS versions 7.4.0 through 7.4.4, versions 7.2.0 through 7.2.8, versions 7.0.0 through 7.0.15, and versions 6.4.0 through 6.4.15 may allow an unauthenticated remote user to consume all system memory via multiple large file uploads.

CVE-2024-46668 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.5 INTEGER OVERFLOW OR WRAPAROUND CWE-190

An Integer Overflow or Wraparound vulnerability in version 7.4.4 and below, version 7.2.10 and below; FortiSASE version 23.4.b FortiOS tenant IPsec IKE service may allow an authenticated attacker to crash the IPsec tunnel via crafted requests, resulting in potential denial-of-service.

CVE-2024-46669 has been assigned to this vulnerability. A CVSS v3 base score of 3.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:A/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:L).

3.2.6 OUT-OF-BOUNDS READ CWE-125

An Out-of-bounds Read vulnerability in FortiOS version 7.6.0, version 7.4.4 and below, version 7.2.9 and below and FortiSASE FortiOS tenant version 24.3.b IPsec IKE service may allow an unauthenticated remote attacker to trigger memory consumption leading to denial-of-service via crafted requests.

CVE-2024-46670 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.7 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22

A improper limitation of a pathname to a restricted directory (‘path traversal’) in Fortinet FortiManager versions 7.6.0 through 7.6.1, 7.4.1 through 7.4.3, FortiOS versions 7.6.0, 7.4.0 through 7.4.4, 7.2.5 through 7.2.9, 7.0.0 through 7.0.15, 6.4.0 through 6.4.15, FortiProxy 7.4.0 through 7.4.5, 7.2.0 through 7.2.11, 7.0.0 through 7.0.18, 2.0.0 through 2.0.14, 1.2.0 through 1.2.13, 1.1.0 through 1.1.6, 1.0.0 through 1.0.7, FortiManager Cloud versions 7.4.1 through 7.4.3 allows attacker to trigger an escalation of privilege via specially crafted packets.

CVE-2024-48884 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.2.8 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22

A improper limitation of a pathname to a restricted directory (‘path traversal’) in Fortinet FortiRecorder versions 7.2.0 through 7.2.1, 7.0.0 through 7.0.4, FortiWeb versions 7.6.0, 7.4.0 through 7.4.4, 7.2.0 through 7.2.10, 7.0.0 through 7.0.10, 6.4.0 through 6.4.3, FortiVoice versions 7.0.0 through 7.0.4, 6.4.0 through 6.4.9, 6.0.0 through 6.0.12 allows attacker to escalate privilege via specially crafted packets.

CVE-2024-48885 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:N/I:N/A:H).

3.2.9 OUT-OF-BOUNDS WRITE CWE-787

A out-of-bounds write in Fortinet FortiOS versions 7.6.0, 7.4.0 through 7.4.6, 7.2.0 through 7.2.10, 7.0.0 through 7.0.16, 6.4.0 through 6.4.15 allows attacker to trigger a denial-of-service via specially crafted packets.

CVE-2024-52963 has been assigned to this vulnerability. A CVSS v3 base score of 3.7 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:L).

3.2.10 IMPROPER NEUTRALIZATION OF CRLF SEQUENCES IN HTTP HEADERS (‘HTTP REQUEST/RESPONSE SPLITTING’) CWE-113

An improper neutralization of crlf sequences in http headers (‘http response splitting’) in Fortinet FortiOS 7.2.0 through 7.6.0, FortiProxy 7.2.0 through 7.4.5 allows attacker to execute unauthorized code or commands via crafted HTTP header.

CVE-2024-54021 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • RUGGEDCOM APE1808: Contact customer support to receive patch and update information.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-770770 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • February 13, 2025: Initial Publication

 Read More

Siemens Opcenter Intelligence

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 9.4
ATTENTION: Exploitable remotely/low attack complexity
Vendor: Siemens
Equipment: Opcenter Intelligence
Vulnerabilities: Improper Authentication, Improper Limitation of a Pathname to a Restricted Directory (‘Path Traversal’), Deserialization of Untrusted Data, Insertion of Sensitive Information into Log File, Server-Side Request Forgery (SSRF)

2. RISK EVALUATION
Successful exploitation of these vulnerabilities could enable an attacker to execute remote code or allow a malicious site administrator to change passwords for users.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:

Siemens Opcenter Intelligence: All versions prior to V2501

3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER AUTHENTICATION CWE-287
Tableau is aware of a broken access control vulnerability present in Tableau Server affecting Tableau Server users using Local Identity Store for managing users. The vulnerability allows a malicious site administrator to change passwords for users in different sites hosted on the same Tableau Server, resulting in the potential for unauthorized access to data. Tableau Server versions affected are: 2020.4.16, 2021.1.13, 2021.2.10, 2021.3.9, 2021.4.4 and earlier. All future releases of Tableau Server will address this security issue. Versions that are no longer supported are not tested and may be vulnerable.
CVE-2022-22127 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:C/C:H/I:H/A:N).
A CVSS v4 score has also been calculated for CVE-2022-22127. A base score of 7.4 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:H/AT:N/PR:H/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N).
3.2.2 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22
Tableau discovered a path traversal vulnerability affecting Tableau Server Administration Agent’s internal file transfer service that could allow remote code execution. Tableau only supports product versions for 24 months after release. Older versions have reached their end of life and are no longer supported. They are also not assessed for potential security issues and do not receive security updates.
CVE-2022-22128 has been assigned to this vulnerability. A CVSS v3 base score of 9.0 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2022-22128. A base score of 9.2 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:H/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.3 DESERIALIZATION OF UNTRUSTED DATA CWE-502
The Java OpenWire protocol marshaller is vulnerable to remote code execution. This vulnerability may allow a remote attacker with network access to either a Java-based OpenWire broker or client to run arbitrary shell commands by manipulating serialized class types in the OpenWire protocol to cause either the client or the broker (respectively) to instantiate any class on the classpath. Users are recommended to upgrade both brokers and clients to version 5.15.16, 5.16.7, 5.17.6, or 5.18.3 which fixes this issue. For Opcenter Intelligence: On November 2, 2023, Apache announced the discovery of CVE-2023-46604, a remote code execution (RCE) vulnerability impacting Apache ActiveMQ clients. As a result of this issue, a remote threat actor with network access to either a Java-based OpenWire broker or client could execute code remotely to run arbitrary shell commands.
CVE-2023-46604 has been assigned to this vulnerability. A CVSS v3 base score of 9.6 has been assigned; the CVSS vector string is (CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2023-46604. A base score of 9.4 has been calculated; the CVSS vector string is (CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H).
3.2.4 INSERTION OF SENSITIVE INFORMATION INTO LOG FILE CWE-532
Personal access token disclosure vulnerability in Tableau Server. For details see Salesforce knowledge article id 000390611.
CVE-2025-26490 has been assigned to this vulnerability. A CVSS v3 base score of 4.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:N).
A CVSS v4 score has also been calculated for CVE-2025-26490. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).
3.2.5 SERVER-SIDE REQUEST FORGERY (SSRF) CWE-918
Server-side request forgery (SSRF) vulnerability in Tableau Server. For details see Salesforce knowledge article id 001534936.
CVE-2025-26491 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:N/A:N).
A CVSS v4 score has also been calculated for CVE-2025-26491. A base score of 7.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
Siemens reported these vulnerabilities to CISA.
4. MITIGATIONS
Siemens recommends Opcenter Intelligence users update to V2501 or later version and install the latest available version of Tableau Server as described in https://support.sw.siemens.com/knowledge-base/PL8822108.
As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.
For more information see the associated Siemens security advisory SSA-246355 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:

Do not click web links or open attachments in unsolicited email messages.
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY

February 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.4
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: Opcenter Intelligence
  • Vulnerabilities: Improper Authentication, Improper Limitation of a Pathname to a Restricted Directory (‘Path Traversal’), Deserialization of Untrusted Data, Insertion of Sensitive Information into Log File, Server-Side Request Forgery (SSRF)

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could enable an attacker to execute remote code or allow a malicious site administrator to change passwords for users.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • Siemens Opcenter Intelligence: All versions prior to V2501

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER AUTHENTICATION CWE-287

Tableau is aware of a broken access control vulnerability present in Tableau Server affecting Tableau Server users using Local Identity Store for managing users. The vulnerability allows a malicious site administrator to change passwords for users in different sites hosted on the same Tableau Server, resulting in the potential for unauthorized access to data. Tableau Server versions affected are: 2020.4.16, 2021.1.13, 2021.2.10, 2021.3.9, 2021.4.4 and earlier. All future releases of Tableau Server will address this security issue. Versions that are no longer supported are not tested and may be vulnerable.

CVE-2022-22127 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:C/C:H/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2022-22127. A base score of 7.4 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:H/AT:N/PR:H/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N).

3.2.2 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22

Tableau discovered a path traversal vulnerability affecting Tableau Server Administration Agent’s internal file transfer service that could allow remote code execution. Tableau only supports product versions for 24 months after release. Older versions have reached their end of life and are no longer supported. They are also not assessed for potential security issues and do not receive security updates.

CVE-2022-22128 has been assigned to this vulnerability. A CVSS v3 base score of 9.0 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2022-22128. A base score of 9.2 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:H/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.3 DESERIALIZATION OF UNTRUSTED DATA CWE-502

The Java OpenWire protocol marshaller is vulnerable to remote code execution. This vulnerability may allow a remote attacker with network access to either a Java-based OpenWire broker or client to run arbitrary shell commands by manipulating serialized class types in the OpenWire protocol to cause either the client or the broker (respectively) to instantiate any class on the classpath. Users are recommended to upgrade both brokers and clients to version 5.15.16, 5.16.7, 5.17.6, or 5.18.3 which fixes this issue. For Opcenter Intelligence: On November 2, 2023, Apache announced the discovery of CVE-2023-46604, a remote code execution (RCE) vulnerability impacting Apache ActiveMQ clients. As a result of this issue, a remote threat actor with network access to either a Java-based OpenWire broker or client could execute code remotely to run arbitrary shell commands.

CVE-2023-46604 has been assigned to this vulnerability. A CVSS v3 base score of 9.6 has been assigned; the CVSS vector string is (CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2023-46604. A base score of 9.4 has been calculated; the CVSS vector string is (CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H).

3.2.4 INSERTION OF SENSITIVE INFORMATION INTO LOG FILE CWE-532

Personal access token disclosure vulnerability in Tableau Server. For details see Salesforce knowledge article id 000390611.

CVE-2025-26490 has been assigned to this vulnerability. A CVSS v3 base score of 4.9 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2025-26490. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.2.5 SERVER-SIDE REQUEST FORGERY (SSRF) CWE-918

Server-side request forgery (SSRF) vulnerability in Tableau Server. For details see Salesforce knowledge article id 001534936.

CVE-2025-26491 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2025-26491. A base score of 7.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens recommends Opcenter Intelligence users update to V2501 or later version and install the latest available version of Tableau Server as described in https://support.sw.siemens.com/knowledge-base/PL8822108.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-246355 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • February 13, 2025: Initial Publication

 Read More

Siemens SIMATIC

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 6.9
ATTENTION: Exploitable remotely/low attack complexity
Vendor: Siemens
Equipment: SIMATIC
Vulnerability: Observable Discrepancy

2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an unauthenticated remote attacker to identify valid usernames.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports the following SIMATIC products are affected:

Siemens SIMATIC S7-1200 CPU 1217C DC/DC/DC (6ES7217-1AG40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1513R-1 PN (6ES7513-1RM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1513pro-2 PN (6ES7513-2PM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1500 CPU 1518-4 PN/DP (6AG1518-4AP00-4AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1517H-3 PN (6ES7517-3HP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1200 CPU 1214FC DC/DC/Rly (6ES7214-1HF40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1200 CPU 1215C DC/DC/Rly (6ES7215-1HG40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1517F-3 PN/DP (6ES7517-3FP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-4XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-2XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1510SP F-1 PN (6ES7510-1SK03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1200 CPU 1212FC DC/DC/DC (6ES7212-1AF40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1215C DC/DC/DC (6ES7215-1AG40-0XB0): vers:all/<V4.7
Siemens SIMATIC Drive Controller CPU 1507D TF (6ES7615-7DF10-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-4XB0): vers:all/<V4.7
Siemens SIPLUS S7-1500 CPU 1517H-3 PN (6AG1517-3HP00-4AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1200 CPU 1211C AC/DC/Rly (6ES7211-1BE40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1516F-3 PN/DP (6ES7516-3FP03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1518-4 PN/DP (6ES7518-4AP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1511C-1 PN (6ES7511-1CL03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1512SP-1 PN (6ES7512-1DM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-2XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1215C DC/DC/DC (6AG1215-1AG40-5XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-2XB0): vers:all/<V4.7
Siemens SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants): vers:all/>=V30.1.0
Siemens SIMATIC S7-1500 CPU 1511-1 PN (6ES7511-1AL03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1515TF-2 PN (6ES7515-2UN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-4XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-2XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1516pro-2 PN (6ES7516-2PP03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-2XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-4XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1212C DC/DC/DC RAIL (6AG2212-1AE40-1XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-2XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1510SP-1 PN (6ES7510-1DK03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1518T-4 PN/DP (6ES7518-4TP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1513F-1 PN (6ES7513-1FM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-5XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1513pro F-2 PN (6ES7513-2GM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1200 CPU 1212C DC/DC/DC (6ES7212-1AE40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1214C AC/DC/Rly (6ES7214-1BG40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1514SP F-2 PN (6ES7514-2SN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1214C DC/DC/DC RAIL (6AG2214-1AG40-1XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1514SPT-2 PN (6ES7514-2VN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-5XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1514SPT F-2 PN (6ES7514-2WN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-5XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1212FC DC/DC/Rly (6ES7212-1HF40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1214FC DC/DC/DC (6AG1214-1AF40-5XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1511TF-1 PN (6ES7511-1UL03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-5XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1214C DC/DC/Rly (6ES7214-1HG40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1211C DC/DC/Rly (6ES7211-1HE40-0XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-5XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1517-3 PN/DP (6ES7517-3AP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-2XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1212C AC/DC/Rly (6ES7212-1BE40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1517TF-3 PN/DP (6ES7517-3UP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1215FC DC/DC/DC (6AG1215-1AF40-5XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1214FC DC/DC/DC (6ES7214-1AF40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1517F-3 PN/DP (6ES7517-3FP01-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1514SP-2 PN (6ES7514-2DN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1200 CPU 1215C AC/DC/Rly (6ES7215-1BG40-0XB0): vers:all/<V4.7
Siemens SIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1518F-4 PN/DP (6ES7518-4FP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1517T-3 PN/DP (6ES7517-3TP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-2XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1511T-1 PN (6ES7511-1TL03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-4XB0): vers:all/<V4.7
Siemens SIMATIC S7-PLCSIM Advanced: vers:all/>=V6.0|<V7.0
Siemens SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-4XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1512SP F-1 PN (6ES7512-1SM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1511F-1 PN (6ES7511-1FL03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1513-1 PN (6ES7513-1AM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1512C-1 PN (6ES7512-1CM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC Drive Controller CPU 1504D TF (6ES7615-4DF10-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1515F-2 PN (6ES7515-2FN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1200 CPU 1215FC DC/DC/DC (6ES7215-1AF40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1518TF-4 PN/DP (6ES7518-4UP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-4XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1515R-2 PN (6ES7515-2RN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1500 CPU 1518HF-4 PN (6AG1518-4JP00-4AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1200 CPU 1215FC DC/DC/Rly (6ES7215-1HF40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1516TF-3 PN/DP (6ES7516-3UN00-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1214FC DC/DC/RLY (6AG1214-1HF40-5XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1515T-2 PN (6ES7515-2TN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-4XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1515-2 PN (6ES7515-2AN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-2XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1211C DC/DC/DC (6ES7211-1AE40-0XB0): vers:all/<V4.7
Siemens SIPLUS S7-1500 CPU 1518F-4 PN/DP (6AG1518-4FP00-4AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1200 CPU 1212C DC/DC/Rly (6ES7212-1HE40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1516-3 PN/DP (6ES7516-3AP03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-4XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1518HF-4 PN (6ES7518-4JP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1200 CPU 1214C DC/DC/DC (6ES7214-1AG40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1500 CPU 1516pro F-2 PN (6ES7516-2GP03-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 CPU 1516T-3 PN/DP (6ES7516-3TN00-0AB0): vers:all/>=V3.1.0|<V3.1.2
Siemens SIMATIC S7-1500 Software Controller: vers:all/>=V30.1.0

3.2 VULNERABILITY OVERVIEW
3.2.1 OBSERVABLE DISCREPANCY CWE-203
The login functionality of the web server in affected devices does not normalize the response times of login attempts. An unauthenticated remote attacker could exploit this side-channel information to distinguish between valid and invalid usernames.
CVE-2023-37482 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).
A CVSS v4 score has also been calculated for CVE-2023-37482. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:N/VA:N/SC:N/SI:N/SA:N).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
David Henrique Estevam de Andrade reported this vulnerability to Siemens.Siemens then reported this vulnerability to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

SIMATIC Drive Controller CPU 1504D TF (6ES7615-4DF10-0AB0), SIMATIC Drive Controller CPU 1507D TF (6ES7615-7DF10-0AB0), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants), SIMATIC S7-1500 CPU 1510SP F-1 PN (6ES7510-1SK03-0AB0), SIMATIC S7-1500 CPU 1510SP-1 PN (6ES7510-1DK03-0AB0), SIMATIC S7-1500 CPU 1511-1 PN (6ES7511-1AL03-0AB0), SIMATIC S7-1500 CPU 1511C-1 PN (6ES7511-1CL03-0AB0), SIMATIC S7-1500 CPU 1511F-1 PN (6ES7511-1FL03-0AB0), SIMATIC S7-1500 CPU 1511T-1 PN (6ES7511-1TL03-0AB0), SIMATIC S7-1500 CPU 1511TF-1 PN (6ES7511-1UL03-0AB0), SIMATIC S7-1500 CPU 1512C-1 PN (6ES7512-1CM03-0AB0), SIMATIC S7-1500 CPU 1512SP F-1 PN (6ES7512-1SM03-0AB0), SIMATIC S7-1500 CPU 1512SP-1 PN (6ES7512-1DM03-0AB0), SIMATIC S7-1500 CPU 1513-1 PN (6ES7513-1AM03-0AB0), SIMATIC S7-1500 CPU 1513F-1 PN (6ES7513-1FM03-0AB0), SIMATIC S7-1500 CPU 1513pro F-2 PN (6ES7513-2GM03-0AB0), SIMATIC S7-1500 CPU 1513pro-2 PN (6ES7513-2PM03-0AB0), SIMATIC S7-1500 CPU 1513R-1 PN (6ES7513-1RM03-0AB0), SIMATIC S7-1500 CPU 1514SP F-2 PN (6ES7514-2SN03-0AB0), SIMATIC S7-1500 CPU 1514SP-2 PN (6ES7514-2DN03-0AB0), SIMATIC S7-1500 CPU 1514SPT F-2 PN (6ES7514-2WN03-0AB0), SIMATIC S7-1500 CPU 1514SPT-2 PN (6ES7514-2VN03-0AB0), SIMATIC S7-1500 CPU 1515-2 PN (6ES7515-2AN03-0AB0), SIMATIC S7-1500 CPU 1515F-2 PN (6ES7515-2FN03-0AB0), SIMATIC S7-1500 CPU 1515R-2 PN (6ES7515-2RN03-0AB0), SIMATIC S7-1500 CPU 1515T-2 PN (6ES7515-2TN03-0AB0), SIMATIC S7-1500 CPU 1515TF-2 PN (6ES7515-2UN03-0AB0), SIMATIC S7-1500 CPU 1516-3 PN/DP (6ES7516-3AP03-0AB0), SIMATIC S7-1500 CPU 1516F-3 PN/DP (6ES7516-3FP03-0AB0), SIMATIC S7-1500 CPU 1516pro F-2 PN (6ES7516-2GP03-0AB0), SIMATIC S7-1500 CPU 1516pro-2 PN (6ES7516-2PP03-0AB0), SIMATIC S7-1500 CPU 1516T-3 PN/DP (6ES7516-3TN00-0AB0), SIMATIC S7-1500 CPU 1516TF-3 PN/DP (6ES7516-3UN00-0AB0), SIMATIC S7-1500 CPU 1517-3 PN/DP (6ES7517-3AP00-0AB0), SIMATIC S7-1500 CPU 1517F-3 PN/DP (6ES7517-3FP00-0AB0), SIMATIC S7-1500 CPU 1517F-3 PN/DP (6ES7517-3FP01-0AB0), SIMATIC S7-1500 CPU 1517H-3 PN (6ES7517-3HP00-0AB0), SIMATIC S7-1500 CPU 1517T-3 PN/DP (6ES7517-3TP00-0AB0), SIMATIC S7-1500 CPU 1517TF-3 PN/DP (6ES7517-3UP00-0AB0), SIMATIC S7-1500 CPU 1518-4 PN/DP (6ES7518-4AP00-0AB0), SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0), SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0), SIMATIC S7-1500 CPU 1518F-4 PN/DP (6ES7518-4FP00-0AB0), SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0), SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0), SIMATIC S7-1500 CPU 1518HF-4 PN (6ES7518-4JP00-0AB0), SIMATIC S7-1500 CPU 1518T-4 PN/DP (6ES7518-4TP00-0AB0), SIMATIC S7-1500 CPU 1518TF-4 PN/DP (6ES7518-4UP00-0AB0), SIMATIC S7-1500 Software Controller, SIMATIC S7-PLCSIM Advanced, SIPLUS S7-1500 CPU 1517H-3 PN (6AG1517-3HP00-4AB0), SIPLUS S7-1500 CPU 1518-4 PN/DP (6AG1518-4AP00-4AB0), SIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0), SIPLUS S7-1500 CPU 1518F-4 PN/DP (6AG1518-4FP00-4AB0), SIPLUS S7-1500 CPU 1518HF-4 PN (6AG1518-4JP00-4AB0): Disable HTTP (Port 80/tcp) and provide web service access through HTTPS (Port 443/tcp) only; the vulnerability is considered as only exploitable via HTTP.
SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants), SIMATIC S7-1500 Software Controller: Currently no fix is available.
SIMATIC S7-1500 CPU 1510SP F-1 PN (6ES7510-1SK03-0AB0), SIMATIC S7-1500 CPU 1510SP-1 PN (6ES7510-1DK03-0AB0), SIMATIC S7-1500 CPU 1511-1 PN (6ES7511-1AL03-0AB0), SIMATIC S7-1500 CPU 1511C-1 PN (6ES7511-1CL03-0AB0), SIMATIC S7-1500 CPU 1511F-1 PN (6ES7511-1FL03-0AB0), SIMATIC S7-1500 CPU 1511T-1 PN (6ES7511-1TL03-0AB0), SIMATIC S7-1500 CPU 1511TF-1 PN (6ES7511-1UL03-0AB0), SIMATIC S7-1500 CPU 1512C-1 PN (6ES7512-1CM03-0AB0), SIMATIC S7-1500 CPU 1512SP F-1 PN (6ES7512-1SM03-0AB0), SIMATIC S7-1500 CPU 1512SP-1 PN (6ES7512-1DM03-0AB0), SIMATIC S7-1500 CPU 1513-1 PN (6ES7513-1AM03-0AB0), SIMATIC S7-1500 CPU 1513F-1 PN (6ES7513-1FM03-0AB0), SIMATIC S7-1500 CPU 1513pro F-2 PN (6ES7513-2GM03-0AB0), SIMATIC S7-1500 CPU 1513pro-2 PN (6ES7513-2PM03-0AB0), SIMATIC S7-1500 CPU 1513R-1 PN (6ES7513-1RM03-0AB0), SIMATIC S7-1500 CPU 1514SP F-2 PN (6ES7514-2SN03-0AB0), SIMATIC S7-1500 CPU 1514SP-2 PN (6ES7514-2DN03-0AB0), SIMATIC S7-1500 CPU 1514SPT F-2 PN (6ES7514-2WN03-0AB0), SIMATIC S7-1500 CPU 1514SPT-2 PN (6ES7514-2VN03-0AB0), SIMATIC S7-1500 CPU 1515-2 PN (6ES7515-2AN03-0AB0), SIMATIC S7-1500 CPU 1515F-2 PN (6ES7515-2FN03-0AB0), SIMATIC S7-1500 CPU 1515R-2 PN (6ES7515-2RN03-0AB0), SIMATIC S7-1500 CPU 1515T-2 PN (6ES7515-2TN03-0AB0), SIMATIC S7-1500 CPU 1515TF-2 PN (6ES7515-2UN03-0AB0), SIMATIC S7-1500 CPU 1516-3 PN/DP (6ES7516-3AP03-0AB0), SIMATIC S7-1500 CPU 1516F-3 PN/DP (6ES7516-3FP03-0AB0), SIMATIC S7-1500 CPU 1516pro F-2 PN (6ES7516-2GP03-0AB0), SIMATIC S7-1500 CPU 1516pro-2 PN (6ES7516-2PP03-0AB0), SIMATIC S7-1500 CPU 1516T-3 PN/DP (6ES7516-3TN00-0AB0), SIMATIC S7-1500 CPU 1516TF-3 PN/DP (6ES7516-3UN00-0AB0), SIMATIC S7-1500 CPU 1517-3 PN/DP (6ES7517-3AP00-0AB0), SIMATIC S7-1500 CPU 1517F-3 PN/DP (6ES7517-3FP00-0AB0), SIMATIC S7-1500 CPU 1517F-3 PN/DP (6ES7517-3FP01-0AB0), SIMATIC S7-1500 CPU 1517H-3 PN (6ES7517-3HP00-0AB0), SIMATIC S7-1500 CPU 1517T-3 PN/DP (6ES7517-3TP00-0AB0), SIMATIC S7-1500 CPU 1517TF-3 PN/DP (6ES7517-3UP00-0AB0), SIMATIC S7-1500 CPU 1518-4 PN/DP (6ES7518-4AP00-0AB0), SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0), SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0), SIMATIC S7-1500 CPU 1518F-4 PN/DP (6ES7518-4FP00-0AB0), SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0), SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0), SIMATIC S7-1500 CPU 1518HF-4 PN (6ES7518-4JP00-0AB0), SIMATIC S7-1500 CPU 1518T-4 PN/DP (6ES7518-4TP00-0AB0), SIMATIC S7-1500 CPU 1518TF-4 PN/DP (6ES7518-4UP00-0AB0), SIPLUS S7-1500 CPU 1517H-3 PN (6AG1517-3HP00-4AB0), SIPLUS S7-1500 CPU 1518-4 PN/DP (6AG1518-4AP00-4AB0), SIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0), SIPLUS S7-1500 CPU 1518F-4 PN/DP (6AG1518-4FP00-4AB0), SIPLUS S7-1500 CPU 1518HF-4 PN (6AG1518-4JP00-4AB0): Update to V3.1.2 or a later version.
SIMATIC Drive Controller CPU 1504D TF (6ES7615-4DF10-0AB0), SIMATIC Drive Controller CPU 1507D TF (6ES7615-7DF10-0AB0): Update to V3.1.2 or later version.
SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-2XB0), SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-4XB0), SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-2XB0), SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-4XB0), SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-2XB0), SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-4XB0), SIPLUS S7-1200 CPU 1212C DC/DC/DC RAIL (6AG2212-1AE40-1XB0), SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-2XB0), SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-4XB0), SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-5XB0), SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-2XB0), SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-4XB0), SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-5XB0), SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-2XB0), SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-4XB0), SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-5XB0), SIPLUS S7-1200 CPU 1214C DC/DC/DC RAIL (6AG2214-1AG40-1XB0), SIPLUS S7-1200 CPU 1214FC DC/DC/DC (6AG1214-1AF40-5XB0), SIPLUS S7-1200 CPU 1214FC DC/DC/RLY (6AG1214-1HF40-5XB0), SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-2XB0), SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-4XB0), SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-5XB0), SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-2XB0), SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-4XB0), SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-2XB0), SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-4XB0), SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-5XB0), SIPLUS S7-1200 CPU 1215C DC/DC/DC (6AG1215-1AG40-5XB0), SIPLUS S7-1200 CPU 1215FC DC/DC/DC (6AG1215-1AF40-5XB0): Update to V4.7 or a later version.
SIMATIC S7-1200 CPU 1211C AC/DC/Rly (6ES7211-1BE40-0XB0), SIMATIC S7-1200 CPU 1211C DC/DC/DC (6ES7211-1AE40-0XB0), SIMATIC S7-1200 CPU 1211C DC/DC/Rly (6ES7211-1HE40-0XB0), SIMATIC S7-1200 CPU 1212C AC/DC/Rly (6ES7212-1BE40-0XB0), SIMATIC S7-1200 CPU 1212C DC/DC/DC (6ES7212-1AE40-0XB0), SIMATIC S7-1200 CPU 1212C DC/DC/Rly (6ES7212-1HE40-0XB0), SIMATIC S7-1200 CPU 1212FC DC/DC/DC (6ES7212-1AF40-0XB0), SIMATIC S7-1200 CPU 1212FC DC/DC/Rly (6ES7212-1HF40-0XB0), SIMATIC S7-1200 CPU 1214C AC/DC/Rly (6ES7214-1BG40-0XB0), SIMATIC S7-1200 CPU 1214C DC/DC/DC (6ES7214-1AG40-0XB0), SIMATIC S7-1200 CPU 1214C DC/DC/Rly (6ES7214-1HG40-0XB0), SIMATIC S7-1200 CPU 1214FC DC/DC/DC (6ES7214-1AF40-0XB0), SIMATIC S7-1200 CPU 1214FC DC/DC/Rly (6ES7214-1HF40-0XB0), SIMATIC S7-1200 CPU 1215C AC/DC/Rly (6ES7215-1BG40-0XB0), SIMATIC S7-1200 CPU 1215C DC/DC/DC (6ES7215-1AG40-0XB0), SIMATIC S7-1200 CPU 1215C DC/DC/Rly (6ES7215-1HG40-0XB0), SIMATIC S7-1200 CPU 1215FC DC/DC/DC (6ES7215-1AF40-0XB0), SIMATIC S7-1200 CPU 1215FC DC/DC/Rly (6ES7215-1HF40-0XB0), SIMATIC S7-1200 CPU 1217C DC/DC/DC (6ES7217-1AG40-0XB0): Update to V4.7 or a later version.
SIMATIC S7-PLCSIM Advanced: Update to V7.0 or a later version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.
For more information see the associated Siemens security advisory SSA-195895 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.
5. UPDATE HISTORY

February 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 6.9
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SIMATIC
  • Vulnerability: Observable Discrepancy

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an unauthenticated remote attacker to identify valid usernames.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports the following SIMATIC products are affected:

  • Siemens SIMATIC S7-1200 CPU 1217C DC/DC/DC (6ES7217-1AG40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1513R-1 PN (6ES7513-1RM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1513pro-2 PN (6ES7513-2PM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1500 CPU 1518-4 PN/DP (6AG1518-4AP00-4AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1517H-3 PN (6ES7517-3HP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1200 CPU 1214FC DC/DC/Rly (6ES7214-1HF40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1200 CPU 1215C DC/DC/Rly (6ES7215-1HG40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1517F-3 PN/DP (6ES7517-3FP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-4XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-2XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1510SP F-1 PN (6ES7510-1SK03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1200 CPU 1212FC DC/DC/DC (6ES7212-1AF40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1215C DC/DC/DC (6ES7215-1AG40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC Drive Controller CPU 1507D TF (6ES7615-7DF10-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-4XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1500 CPU 1517H-3 PN (6AG1517-3HP00-4AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1200 CPU 1211C AC/DC/Rly (6ES7211-1BE40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1516F-3 PN/DP (6ES7516-3FP03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1518-4 PN/DP (6ES7518-4AP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1511C-1 PN (6ES7511-1CL03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1512SP-1 PN (6ES7512-1DM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-2XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1215C DC/DC/DC (6AG1215-1AG40-5XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-2XB0): vers:all/<V4.7
  • Siemens SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants): vers:all/>=V30.1.0
  • Siemens SIMATIC S7-1500 CPU 1511-1 PN (6ES7511-1AL03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1515TF-2 PN (6ES7515-2UN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-4XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-2XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1516pro-2 PN (6ES7516-2PP03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-2XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-4XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1212C DC/DC/DC RAIL (6AG2212-1AE40-1XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-2XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1510SP-1 PN (6ES7510-1DK03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1518T-4 PN/DP (6ES7518-4TP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1513F-1 PN (6ES7513-1FM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-5XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1513pro F-2 PN (6ES7513-2GM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1200 CPU 1212C DC/DC/DC (6ES7212-1AE40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1214C AC/DC/Rly (6ES7214-1BG40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1514SP F-2 PN (6ES7514-2SN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1214C DC/DC/DC RAIL (6AG2214-1AG40-1XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1514SPT-2 PN (6ES7514-2VN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-5XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1514SPT F-2 PN (6ES7514-2WN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-5XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1212FC DC/DC/Rly (6ES7212-1HF40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1214FC DC/DC/DC (6AG1214-1AF40-5XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1511TF-1 PN (6ES7511-1UL03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-5XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1214C DC/DC/Rly (6ES7214-1HG40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1211C DC/DC/Rly (6ES7211-1HE40-0XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-5XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1517-3 PN/DP (6ES7517-3AP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-2XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1212C AC/DC/Rly (6ES7212-1BE40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1517TF-3 PN/DP (6ES7517-3UP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1215FC DC/DC/DC (6AG1215-1AF40-5XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1214FC DC/DC/DC (6ES7214-1AF40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1517F-3 PN/DP (6ES7517-3FP01-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1514SP-2 PN (6ES7514-2DN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1200 CPU 1215C AC/DC/Rly (6ES7215-1BG40-0XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1518F-4 PN/DP (6ES7518-4FP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1517T-3 PN/DP (6ES7517-3TP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-2XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1511T-1 PN (6ES7511-1TL03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-4XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-PLCSIM Advanced: vers:all/>=V6.0|<V7.0
  • Siemens SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-4XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1512SP F-1 PN (6ES7512-1SM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1511F-1 PN (6ES7511-1FL03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1513-1 PN (6ES7513-1AM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1512C-1 PN (6ES7512-1CM03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC Drive Controller CPU 1504D TF (6ES7615-4DF10-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1515F-2 PN (6ES7515-2FN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1200 CPU 1215FC DC/DC/DC (6ES7215-1AF40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1518TF-4 PN/DP (6ES7518-4UP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-4XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1515R-2 PN (6ES7515-2RN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1500 CPU 1518HF-4 PN (6AG1518-4JP00-4AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1200 CPU 1215FC DC/DC/Rly (6ES7215-1HF40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1516TF-3 PN/DP (6ES7516-3UN00-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1214FC DC/DC/RLY (6AG1214-1HF40-5XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1515T-2 PN (6ES7515-2TN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-4XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1515-2 PN (6ES7515-2AN03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-2XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1211C DC/DC/DC (6ES7211-1AE40-0XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1500 CPU 1518F-4 PN/DP (6AG1518-4FP00-4AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1200 CPU 1212C DC/DC/Rly (6ES7212-1HE40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1516-3 PN/DP (6ES7516-3AP03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-4XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1518HF-4 PN (6ES7518-4JP00-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1200 CPU 1214C DC/DC/DC (6ES7214-1AG40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1500 CPU 1516pro F-2 PN (6ES7516-2GP03-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 CPU 1516T-3 PN/DP (6ES7516-3TN00-0AB0): vers:all/>=V3.1.0|<V3.1.2
  • Siemens SIMATIC S7-1500 Software Controller: vers:all/>=V30.1.0

3.2 VULNERABILITY OVERVIEW

3.2.1 OBSERVABLE DISCREPANCY CWE-203

The login functionality of the web server in affected devices does not normalize the response times of login attempts. An unauthenticated remote attacker could exploit this side-channel information to distinguish between valid and invalid usernames.

CVE-2023-37482 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2023-37482. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:N/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

David Henrique Estevam de Andrade reported this vulnerability to Siemens.
Siemens then reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • SIMATIC Drive Controller CPU 1504D TF (6ES7615-4DF10-0AB0), SIMATIC Drive Controller CPU 1507D TF (6ES7615-7DF10-0AB0), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants), SIMATIC S7-1500 CPU 1510SP F-1 PN (6ES7510-1SK03-0AB0), SIMATIC S7-1500 CPU 1510SP-1 PN (6ES7510-1DK03-0AB0), SIMATIC S7-1500 CPU 1511-1 PN (6ES7511-1AL03-0AB0), SIMATIC S7-1500 CPU 1511C-1 PN (6ES7511-1CL03-0AB0), SIMATIC S7-1500 CPU 1511F-1 PN (6ES7511-1FL03-0AB0), SIMATIC S7-1500 CPU 1511T-1 PN (6ES7511-1TL03-0AB0), SIMATIC S7-1500 CPU 1511TF-1 PN (6ES7511-1UL03-0AB0), SIMATIC S7-1500 CPU 1512C-1 PN (6ES7512-1CM03-0AB0), SIMATIC S7-1500 CPU 1512SP F-1 PN (6ES7512-1SM03-0AB0), SIMATIC S7-1500 CPU 1512SP-1 PN (6ES7512-1DM03-0AB0), SIMATIC S7-1500 CPU 1513-1 PN (6ES7513-1AM03-0AB0), SIMATIC S7-1500 CPU 1513F-1 PN (6ES7513-1FM03-0AB0), SIMATIC S7-1500 CPU 1513pro F-2 PN (6ES7513-2GM03-0AB0), SIMATIC S7-1500 CPU 1513pro-2 PN (6ES7513-2PM03-0AB0), SIMATIC S7-1500 CPU 1513R-1 PN (6ES7513-1RM03-0AB0), SIMATIC S7-1500 CPU 1514SP F-2 PN (6ES7514-2SN03-0AB0), SIMATIC S7-1500 CPU 1514SP-2 PN (6ES7514-2DN03-0AB0), SIMATIC S7-1500 CPU 1514SPT F-2 PN (6ES7514-2WN03-0AB0), SIMATIC S7-1500 CPU 1514SPT-2 PN (6ES7514-2VN03-0AB0), SIMATIC S7-1500 CPU 1515-2 PN (6ES7515-2AN03-0AB0), SIMATIC S7-1500 CPU 1515F-2 PN (6ES7515-2FN03-0AB0), SIMATIC S7-1500 CPU 1515R-2 PN (6ES7515-2RN03-0AB0), SIMATIC S7-1500 CPU 1515T-2 PN (6ES7515-2TN03-0AB0), SIMATIC S7-1500 CPU 1515TF-2 PN (6ES7515-2UN03-0AB0), SIMATIC S7-1500 CPU 1516-3 PN/DP (6ES7516-3AP03-0AB0), SIMATIC S7-1500 CPU 1516F-3 PN/DP (6ES7516-3FP03-0AB0), SIMATIC S7-1500 CPU 1516pro F-2 PN (6ES7516-2GP03-0AB0), SIMATIC S7-1500 CPU 1516pro-2 PN (6ES7516-2PP03-0AB0), SIMATIC S7-1500 CPU 1516T-3 PN/DP (6ES7516-3TN00-0AB0), SIMATIC S7-1500 CPU 1516TF-3 PN/DP (6ES7516-3UN00-0AB0), SIMATIC S7-1500 CPU 1517-3 PN/DP (6ES7517-3AP00-0AB0), SIMATIC S7-1500 CPU 1517F-3 PN/DP (6ES7517-3FP00-0AB0), SIMATIC S7-1500 CPU 1517F-3 PN/DP (6ES7517-3FP01-0AB0), SIMATIC S7-1500 CPU 1517H-3 PN (6ES7517-3HP00-0AB0), SIMATIC S7-1500 CPU 1517T-3 PN/DP (6ES7517-3TP00-0AB0), SIMATIC S7-1500 CPU 1517TF-3 PN/DP (6ES7517-3UP00-0AB0), SIMATIC S7-1500 CPU 1518-4 PN/DP (6ES7518-4AP00-0AB0), SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0), SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0), SIMATIC S7-1500 CPU 1518F-4 PN/DP (6ES7518-4FP00-0AB0), SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0), SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0), SIMATIC S7-1500 CPU 1518HF-4 PN (6ES7518-4JP00-0AB0), SIMATIC S7-1500 CPU 1518T-4 PN/DP (6ES7518-4TP00-0AB0), SIMATIC S7-1500 CPU 1518TF-4 PN/DP (6ES7518-4UP00-0AB0), SIMATIC S7-1500 Software Controller, SIMATIC S7-PLCSIM Advanced, SIPLUS S7-1500 CPU 1517H-3 PN (6AG1517-3HP00-4AB0), SIPLUS S7-1500 CPU 1518-4 PN/DP (6AG1518-4AP00-4AB0), SIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0), SIPLUS S7-1500 CPU 1518F-4 PN/DP (6AG1518-4FP00-4AB0), SIPLUS S7-1500 CPU 1518HF-4 PN (6AG1518-4JP00-4AB0): Disable HTTP (Port 80/tcp) and provide web service access through HTTPS (Port 443/tcp) only; the vulnerability is considered as only exploitable via HTTP.
  • SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants), SIMATIC S7-1500 Software Controller: Currently no fix is available.
  • SIMATIC S7-1500 CPU 1510SP F-1 PN (6ES7510-1SK03-0AB0), SIMATIC S7-1500 CPU 1510SP-1 PN (6ES7510-1DK03-0AB0), SIMATIC S7-1500 CPU 1511-1 PN (6ES7511-1AL03-0AB0), SIMATIC S7-1500 CPU 1511C-1 PN (6ES7511-1CL03-0AB0), SIMATIC S7-1500 CPU 1511F-1 PN (6ES7511-1FL03-0AB0), SIMATIC S7-1500 CPU 1511T-1 PN (6ES7511-1TL03-0AB0), SIMATIC S7-1500 CPU 1511TF-1 PN (6ES7511-1UL03-0AB0), SIMATIC S7-1500 CPU 1512C-1 PN (6ES7512-1CM03-0AB0), SIMATIC S7-1500 CPU 1512SP F-1 PN (6ES7512-1SM03-0AB0), SIMATIC S7-1500 CPU 1512SP-1 PN (6ES7512-1DM03-0AB0), SIMATIC S7-1500 CPU 1513-1 PN (6ES7513-1AM03-0AB0), SIMATIC S7-1500 CPU 1513F-1 PN (6ES7513-1FM03-0AB0), SIMATIC S7-1500 CPU 1513pro F-2 PN (6ES7513-2GM03-0AB0), SIMATIC S7-1500 CPU 1513pro-2 PN (6ES7513-2PM03-0AB0), SIMATIC S7-1500 CPU 1513R-1 PN (6ES7513-1RM03-0AB0), SIMATIC S7-1500 CPU 1514SP F-2 PN (6ES7514-2SN03-0AB0), SIMATIC S7-1500 CPU 1514SP-2 PN (6ES7514-2DN03-0AB0), SIMATIC S7-1500 CPU 1514SPT F-2 PN (6ES7514-2WN03-0AB0), SIMATIC S7-1500 CPU 1514SPT-2 PN (6ES7514-2VN03-0AB0), SIMATIC S7-1500 CPU 1515-2 PN (6ES7515-2AN03-0AB0), SIMATIC S7-1500 CPU 1515F-2 PN (6ES7515-2FN03-0AB0), SIMATIC S7-1500 CPU 1515R-2 PN (6ES7515-2RN03-0AB0), SIMATIC S7-1500 CPU 1515T-2 PN (6ES7515-2TN03-0AB0), SIMATIC S7-1500 CPU 1515TF-2 PN (6ES7515-2UN03-0AB0), SIMATIC S7-1500 CPU 1516-3 PN/DP (6ES7516-3AP03-0AB0), SIMATIC S7-1500 CPU 1516F-3 PN/DP (6ES7516-3FP03-0AB0), SIMATIC S7-1500 CPU 1516pro F-2 PN (6ES7516-2GP03-0AB0), SIMATIC S7-1500 CPU 1516pro-2 PN (6ES7516-2PP03-0AB0), SIMATIC S7-1500 CPU 1516T-3 PN/DP (6ES7516-3TN00-0AB0), SIMATIC S7-1500 CPU 1516TF-3 PN/DP (6ES7516-3UN00-0AB0), SIMATIC S7-1500 CPU 1517-3 PN/DP (6ES7517-3AP00-0AB0), SIMATIC S7-1500 CPU 1517F-3 PN/DP (6ES7517-3FP00-0AB0), SIMATIC S7-1500 CPU 1517F-3 PN/DP (6ES7517-3FP01-0AB0), SIMATIC S7-1500 CPU 1517H-3 PN (6ES7517-3HP00-0AB0), SIMATIC S7-1500 CPU 1517T-3 PN/DP (6ES7517-3TP00-0AB0), SIMATIC S7-1500 CPU 1517TF-3 PN/DP (6ES7517-3UP00-0AB0), SIMATIC S7-1500 CPU 1518-4 PN/DP (6ES7518-4AP00-0AB0), SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AB0), SIMATIC S7-1500 CPU 1518-4 PN/DP MFP (6ES7518-4AX00-1AC0), SIMATIC S7-1500 CPU 1518F-4 PN/DP (6ES7518-4FP00-0AB0), SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AB0), SIMATIC S7-1500 CPU 1518F-4 PN/DP MFP (6ES7518-4FX00-1AC0), SIMATIC S7-1500 CPU 1518HF-4 PN (6ES7518-4JP00-0AB0), SIMATIC S7-1500 CPU 1518T-4 PN/DP (6ES7518-4TP00-0AB0), SIMATIC S7-1500 CPU 1518TF-4 PN/DP (6ES7518-4UP00-0AB0), SIPLUS S7-1500 CPU 1517H-3 PN (6AG1517-3HP00-4AB0), SIPLUS S7-1500 CPU 1518-4 PN/DP (6AG1518-4AP00-4AB0), SIPLUS S7-1500 CPU 1518-4 PN/DP MFP (6AG1518-4AX00-4AC0), SIPLUS S7-1500 CPU 1518F-4 PN/DP (6AG1518-4FP00-4AB0), SIPLUS S7-1500 CPU 1518HF-4 PN (6AG1518-4JP00-4AB0): Update to V3.1.2 or a later version.
  • SIMATIC Drive Controller CPU 1504D TF (6ES7615-4DF10-0AB0), SIMATIC Drive Controller CPU 1507D TF (6ES7615-7DF10-0AB0): Update to V3.1.2 or later version.
  • SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-2XB0), SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-4XB0), SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-2XB0), SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-4XB0), SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-2XB0), SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-4XB0), SIPLUS S7-1200 CPU 1212C DC/DC/DC RAIL (6AG2212-1AE40-1XB0), SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-2XB0), SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-4XB0), SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-5XB0), SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-2XB0), SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-4XB0), SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-5XB0), SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-2XB0), SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-4XB0), SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-5XB0), SIPLUS S7-1200 CPU 1214C DC/DC/DC RAIL (6AG2214-1AG40-1XB0), SIPLUS S7-1200 CPU 1214FC DC/DC/DC (6AG1214-1AF40-5XB0), SIPLUS S7-1200 CPU 1214FC DC/DC/RLY (6AG1214-1HF40-5XB0), SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-2XB0), SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-4XB0), SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-5XB0), SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-2XB0), SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-4XB0), SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-2XB0), SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-4XB0), SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-5XB0), SIPLUS S7-1200 CPU 1215C DC/DC/DC (6AG1215-1AG40-5XB0), SIPLUS S7-1200 CPU 1215FC DC/DC/DC (6AG1215-1AF40-5XB0): Update to V4.7 or a later version.
  • SIMATIC S7-1200 CPU 1211C AC/DC/Rly (6ES7211-1BE40-0XB0), SIMATIC S7-1200 CPU 1211C DC/DC/DC (6ES7211-1AE40-0XB0), SIMATIC S7-1200 CPU 1211C DC/DC/Rly (6ES7211-1HE40-0XB0), SIMATIC S7-1200 CPU 1212C AC/DC/Rly (6ES7212-1BE40-0XB0), SIMATIC S7-1200 CPU 1212C DC/DC/DC (6ES7212-1AE40-0XB0), SIMATIC S7-1200 CPU 1212C DC/DC/Rly (6ES7212-1HE40-0XB0), SIMATIC S7-1200 CPU 1212FC DC/DC/DC (6ES7212-1AF40-0XB0), SIMATIC S7-1200 CPU 1212FC DC/DC/Rly (6ES7212-1HF40-0XB0), SIMATIC S7-1200 CPU 1214C AC/DC/Rly (6ES7214-1BG40-0XB0), SIMATIC S7-1200 CPU 1214C DC/DC/DC (6ES7214-1AG40-0XB0), SIMATIC S7-1200 CPU 1214C DC/DC/Rly (6ES7214-1HG40-0XB0), SIMATIC S7-1200 CPU 1214FC DC/DC/DC (6ES7214-1AF40-0XB0), SIMATIC S7-1200 CPU 1214FC DC/DC/Rly (6ES7214-1HF40-0XB0), SIMATIC S7-1200 CPU 1215C AC/DC/Rly (6ES7215-1BG40-0XB0), SIMATIC S7-1200 CPU 1215C DC/DC/DC (6ES7215-1AG40-0XB0), SIMATIC S7-1200 CPU 1215C DC/DC/Rly (6ES7215-1HG40-0XB0), SIMATIC S7-1200 CPU 1215FC DC/DC/DC (6ES7215-1AF40-0XB0), SIMATIC S7-1200 CPU 1215FC DC/DC/Rly (6ES7215-1HF40-0XB0), SIMATIC S7-1200 CPU 1217C DC/DC/DC (6ES7217-1AG40-0XB0): Update to V4.7 or a later version.
  • SIMATIC S7-PLCSIM Advanced: Update to V7.0 or a later version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-195895 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • February 13, 2025: Initial Publication

 Read More

Siemens SIMATIC IPC DiagBase and SIMATIC IPC DiagMonitor

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 7.3
ATTENTION: Exploitable locally
Vendor: Siemens
Equipment: SIMATIC IPC DiagBase and SIMATIC IPC DiagMonitor
Vulnerability: Incorrect Permission Assignment for Critical Resource

2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an authenticated attacker to achieve privilege escalation or bypass security measures.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:

SMATIC IPC DiagMonitor: All versions
SIMATIC IPC DiagBase: All versions

3.2 VULNERABILITY OVERVIEW
3.2.1 INCORRECT PERMISSION ASSIGNMENT FOR CRITICAL RESOURCE CWE-732
The affected device do not properly restrict the user permission for the registry key. This could allow an authenticated attacker to load vulnerable drivers into the system leading to privilege escalation or bypassing endpoint protection and other security measures.
CVE-2025-23403 has been assigned to this vulnerability. A CVSS v3 base score of 7.0 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-23403. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
Siemens reported this vulnerability to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

Remove the user privilege by modifying the registry manually or running a script. For more information refer the FAQ section at: https://support.industry.siemens.com/cs/document/109978178

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage
For more information see the associated Siemens security advisory SSA-369369 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:

Do not click web links or open attachments in unsolicited email messages.
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely. This vulnerability has a high attack complexity.
5. UPDATE HISTORY

February 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.3
  • ATTENTION: Exploitable locally
  • Vendor: Siemens
  • Equipment: SIMATIC IPC DiagBase and SIMATIC IPC DiagMonitor
  • Vulnerability: Incorrect Permission Assignment for Critical Resource

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an authenticated attacker to achieve privilege escalation or bypass security measures.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • SMATIC IPC DiagMonitor: All versions
  • SIMATIC IPC DiagBase: All versions

3.2 VULNERABILITY OVERVIEW

3.2.1 INCORRECT PERMISSION ASSIGNMENT FOR CRITICAL RESOURCE CWE-732

The affected device do not properly restrict the user permission for the registry key. This could allow an authenticated attacker to load vulnerable drivers into the system leading to privilege escalation or bypassing endpoint protection and other security measures.

CVE-2025-23403 has been assigned to this vulnerability. A CVSS v3 base score of 7.0 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-23403. A base score of 7.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:H/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-369369 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely. This vulnerability has a high attack complexity.

5. UPDATE HISTORY

  • February 13, 2025: Initial Publication

 Read More

Siemens SIPROTEC 5

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 5.1
ATTENTION: Low attack complexity
Vendor: Siemens
Equipment: SIPROTEC 5
Vulnerability: Cleartext Storage of Sensitive Information

2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker with physical access to read the sensitive information from the filesystem of the device.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports the following products are affected:

Siemens SIPROTEC 5 7SK85 (CP300): vers:all/*
Siemens SIPROTEC 5 7SJ81 (CP100): vers:all/*
Siemens SIPROTEC 5 7SL86 (CP300): vers:all/*
Siemens SIPROTEC 5 7SL86 (CP200): vers:all/*
Siemens SIPROTEC 5 7SJ86 (CP300): vers:all/*
Siemens SIPROTEC 5 7SK82 (CP100): vers:all/*
Siemens SIPROTEC 5 6MD84 (CP300): vers:all/*
Siemens SIPROTEC 5 7SA87 (CP200): vers:all/*
Siemens SIPROTEC 5 7ST85 (CP300): vers:all/*
Siemens SIPROTEC 5 7SD87 (CP200): vers:all/*
Siemens SIPROTEC 5 7UT87 (CP300): vers:all/*
Siemens SIPROTEC 5 6MD89 (CP300): vers:all/*
Siemens SIPROTEC 5 7SD82 (CP100): vers:all/*
Siemens SIPROTEC 5 6MD85 (CP300): vers:all/*
Siemens SIPROTEC 5 7ST86 (CP300): vers:all/*
Siemens SIPROTEC 5 7SJ82 (CP150): vers:all/*
Siemens SIPROTEC 5 7UT86 (CP200): vers:all/*
Siemens SIPROTEC 5 7SX85 (CP300): vers:all/*
Siemens SIPROTEC 5 7SD87 (CP300): vers:all/*
Siemens SIPROTEC 5 7VU85 (CP300): vers:all/*
Siemens SIPROTEC 5 6MU85 (CP300): vers:all/*
Siemens SIPROTEC 5 7SD86 (CP300): vers:all/*
Siemens SIPROTEC 5 7UT86 (CP300): vers:all/*
Siemens SIPROTEC 5 7VK87 (CP200): vers:all/*
Siemens SIPROTEC 5 7UT85 (CP300): vers:all/*
Siemens SIPROTEC 5 7UT82 (CP150): vers:all/*
Siemens SIPROTEC 5 7SA87 (CP300): vers:all/*
Siemens SIPROTEC 5 7SJ81 (CP150): vers:all/*
Siemens SIPROTEC 5 7SJ82 (CP100): vers:all/*
Siemens SIPROTEC 5 7SA82 (CP100): vers:all/*
Siemens SIPROTEC 5 7UT87 (CP200): vers:all/*
Siemens SIPROTEC 5 7SX82 (CP150): vers:all/*
Siemens SIPROTEC 5 7SD86 (CP200): vers:all/*
Siemens SIPROTEC 5 7SL87 (CP300): vers:all/*
Siemens SIPROTEC 5 6MD85 (CP200): vers:all/*
Siemens SIPROTEC 5 7ST85 (CP200): vers:all/*
Siemens SIPROTEC 5 Compact 7SX800 (CP050): vers:all/*
Siemens SIPROTEC 5 6MD86 (CP300): vers:all/*
Siemens SIPROTEC 5 7SD82 (CP150): vers:all/*
Siemens SIPROTEC 5 7KE85 (CP300): vers:all/*
Siemens SIPROTEC 5 7SL82 (CP100): vers:all/*
Siemens SIPROTEC 5 7SL82 (CP150): vers:all/*
Siemens SIPROTEC 5 7VE85 (CP300): vers:all/*
Siemens SIPROTEC 5 7KE85 (CP200): vers:all/*
Siemens SIPROTEC 5 7SA86 (CP200): vers:all/*
Siemens SIPROTEC 5 7SL87 (CP200): vers:all/*
Siemens SIPROTEC 5 7SY82 (CP150): vers:all/*
Siemens SIPROTEC 5 6MD86 (CP200): vers:all/*
Siemens SIPROTEC 5 7SJ86 (CP200): vers:all/*
Siemens SIPROTEC 5 7SA86 (CP300): vers:all/*
Siemens SIPROTEC 5 7UM85 (CP300): vers:all/*
Siemens SIPROTEC 5 7SS85 (CP300): vers:all/*
Siemens SIPROTEC 5 7SK82 (CP150): vers:all/*
Siemens SIPROTEC 5 7UT82 (CP100): vers:all/*
Siemens SIPROTEC 5 7SS85 (CP200): vers:all/*
Siemens SIPROTEC 5 7SJ85 (CP200): vers:all/*
Siemens SIPROTEC 5 7UT85 (CP200): vers:all/*
Siemens SIPROTEC 5 7SK85 (CP200): vers:all/*
Siemens SIPROTEC 5 7VK87 (CP300): vers:all/*
Siemens SIPROTEC 5 7SJ85 (CP300): vers:all/*
Siemens SIPROTEC 5 7SA82 (CP150): vers:all/*

3.2 VULNERABILITY OVERVIEW
3.2.1 CLEARTEXT STORAGE OF SENSITIVE INFORMATION CWE-312
The affected devices do not encrypt certain data within the on-board flash storage on their PCB. This could allow an attacker with physical access to read the entire filesystem of the device.
CVE-2024-53651 has been assigned to this vulnerability. A CVSS v3 base score of 4.6 has been calculated; the CVSS vector string is (CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).
A CVSS v4 score has also been calculated for CVE-2024-53651. A base score of 5.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
Steffen Robertz, Stefan Viehböck, and Constantin Schieber-Knöbl from SEC Consult Vulnerability Lab reported this vulnerability to Siemens.Siemens then reported this vulnerability to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

All affected products: Limit physical access to affected devices to trusted personnel.
All affected products: Provision certificates signed by customer PKI as described in https://support.industry.siemens.com/cs/document/109768375.
SIPROTEC 5 6MD85 (CP200), SIPROTEC 5 6MD86 (CP200), SIPROTEC 5 7KE85 (CP200), SIPROTEC 5 7SA86 (CP200), SIPROTEC 5 7SA87 (CP200), SIPROTEC 5 7SD86 (CP200), SIPROTEC 5 7SD87 (CP200), SIPROTEC 5 7SJ85 (CP200), SIPROTEC 5 7SJ86 (CP200), SIPROTEC 5 7SK85 (CP200), SIPROTEC 5 7SL86 (CP200), SIPROTEC 5 7SL87 (CP200), SIPROTEC 5 7SS85 (CP200), SIPROTEC 5 7ST85 (CP200), SIPROTEC 5 7UT85 (CP200), SIPROTEC 5 7UT86 (CP200), SIPROTEC 5 7UT87 (CP200), SIPROTEC 5 7VK87 (CP200): Currently no fix is planned.
SIPROTEC 5 6MD84 (CP300), SIPROTEC 5 6MD85 (CP300), SIPROTEC 5 6MD86 (CP300), SIPROTEC 5 6MD89 (CP300), SIPROTEC 5 6MU85 (CP300), SIPROTEC 5 7KE85 (CP300), SIPROTEC 5 7SA82 (CP100), SIPROTEC 5 7SA82 (CP150), SIPROTEC 5 7SA86 (CP300), SIPROTEC 5 7SA87 (CP300), SIPROTEC 5 7SD82 (CP100), SIPROTEC 5 7SD82 (CP150), SIPROTEC 5 7SD86 (CP300), SIPROTEC 5 7SD87 (CP300), SIPROTEC 5 7SJ81 (CP100), SIPROTEC 5 7SJ81 (CP150), SIPROTEC 5 7SJ82 (CP100), SIPROTEC 5 7SJ82 (CP150), SIPROTEC 5 7SJ85 (CP300), SIPROTEC 5 7SJ86 (CP300), SIPROTEC 5 7SK82 (CP100), SIPROTEC 5 7SK82 (CP150), SIPROTEC 5 7SK85 (CP300), SIPROTEC 5 7SL82 (CP100), SIPROTEC 5 7SL82 (CP150), SIPROTEC 5 7SL86 (CP300), SIPROTEC 5 7SL87 (CP300), SIPROTEC 5 7SS85 (CP300), SIPROTEC 5 7ST85 (CP300), SIPROTEC 5 7ST86 (CP300), SIPROTEC 5 7SX82 (CP150), SIPROTEC 5 7SX85 (CP300), SIPROTEC 5 7SY82 (CP150), SIPROTEC 5 7UM85 (CP300), SIPROTEC 5 7UT82 (CP100), SIPROTEC 5 7UT82 (CP150), SIPROTEC 5 7UT85 (CP300), SIPROTEC 5 7UT86 (CP300), SIPROTEC 5 7UT87 (CP300), SIPROTEC 5 7VE85 (CP300), SIPROTEC 5 7VK87 (CP300), SIPROTEC 5 7VU85 (CP300), SIPROTEC 5 Compact 7SX800 (CP050): Currently no fix is available.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.
For more information see the associated Siemens security advisory SSA-111547 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.
5. UPDATE HISTORY

February 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 5.1
  • ATTENTION: Low attack complexity
  • Vendor: Siemens
  • Equipment: SIPROTEC 5
  • Vulnerability: Cleartext Storage of Sensitive Information

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker with physical access to read the sensitive information from the filesystem of the device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports the following products are affected:

  • Siemens SIPROTEC 5 7SK85 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SJ81 (CP100): vers:all/*
  • Siemens SIPROTEC 5 7SL86 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SL86 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7SJ86 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SK82 (CP100): vers:all/*
  • Siemens SIPROTEC 5 6MD84 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SA87 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7ST85 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SD87 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7UT87 (CP300): vers:all/*
  • Siemens SIPROTEC 5 6MD89 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SD82 (CP100): vers:all/*
  • Siemens SIPROTEC 5 6MD85 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7ST86 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SJ82 (CP150): vers:all/*
  • Siemens SIPROTEC 5 7UT86 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7SX85 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SD87 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7VU85 (CP300): vers:all/*
  • Siemens SIPROTEC 5 6MU85 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SD86 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7UT86 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7VK87 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7UT85 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7UT82 (CP150): vers:all/*
  • Siemens SIPROTEC 5 7SA87 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SJ81 (CP150): vers:all/*
  • Siemens SIPROTEC 5 7SJ82 (CP100): vers:all/*
  • Siemens SIPROTEC 5 7SA82 (CP100): vers:all/*
  • Siemens SIPROTEC 5 7UT87 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7SX82 (CP150): vers:all/*
  • Siemens SIPROTEC 5 7SD86 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7SL87 (CP300): vers:all/*
  • Siemens SIPROTEC 5 6MD85 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7ST85 (CP200): vers:all/*
  • Siemens SIPROTEC 5 Compact 7SX800 (CP050): vers:all/*
  • Siemens SIPROTEC 5 6MD86 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SD82 (CP150): vers:all/*
  • Siemens SIPROTEC 5 7KE85 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SL82 (CP100): vers:all/*
  • Siemens SIPROTEC 5 7SL82 (CP150): vers:all/*
  • Siemens SIPROTEC 5 7VE85 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7KE85 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7SA86 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7SL87 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7SY82 (CP150): vers:all/*
  • Siemens SIPROTEC 5 6MD86 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7SJ86 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7SA86 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7UM85 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SS85 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SK82 (CP150): vers:all/*
  • Siemens SIPROTEC 5 7UT82 (CP100): vers:all/*
  • Siemens SIPROTEC 5 7SS85 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7SJ85 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7UT85 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7SK85 (CP200): vers:all/*
  • Siemens SIPROTEC 5 7VK87 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SJ85 (CP300): vers:all/*
  • Siemens SIPROTEC 5 7SA82 (CP150): vers:all/*

3.2 VULNERABILITY OVERVIEW

3.2.1 CLEARTEXT STORAGE OF SENSITIVE INFORMATION CWE-312

The affected devices do not encrypt certain data within the on-board flash storage on their PCB. This could allow an attacker with physical access to read the entire filesystem of the device.

CVE-2024-53651 has been assigned to this vulnerability. A CVSS v3 base score of 4.6 has been calculated; the CVSS vector string is (CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2024-53651. A base score of 5.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Steffen Robertz, Stefan Viehböck, and Constantin Schieber-Knöbl from SEC Consult Vulnerability Lab reported this vulnerability to Siemens.
Siemens then reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • All affected products: Limit physical access to affected devices to trusted personnel.
  • All affected products: Provision certificates signed by customer PKI as described in https://support.industry.siemens.com/cs/document/109768375.
  • SIPROTEC 5 6MD85 (CP200), SIPROTEC 5 6MD86 (CP200), SIPROTEC 5 7KE85 (CP200), SIPROTEC 5 7SA86 (CP200), SIPROTEC 5 7SA87 (CP200), SIPROTEC 5 7SD86 (CP200), SIPROTEC 5 7SD87 (CP200), SIPROTEC 5 7SJ85 (CP200), SIPROTEC 5 7SJ86 (CP200), SIPROTEC 5 7SK85 (CP200), SIPROTEC 5 7SL86 (CP200), SIPROTEC 5 7SL87 (CP200), SIPROTEC 5 7SS85 (CP200), SIPROTEC 5 7ST85 (CP200), SIPROTEC 5 7UT85 (CP200), SIPROTEC 5 7UT86 (CP200), SIPROTEC 5 7UT87 (CP200), SIPROTEC 5 7VK87 (CP200): Currently no fix is planned.
  • SIPROTEC 5 6MD84 (CP300), SIPROTEC 5 6MD85 (CP300), SIPROTEC 5 6MD86 (CP300), SIPROTEC 5 6MD89 (CP300), SIPROTEC 5 6MU85 (CP300), SIPROTEC 5 7KE85 (CP300), SIPROTEC 5 7SA82 (CP100), SIPROTEC 5 7SA82 (CP150), SIPROTEC 5 7SA86 (CP300), SIPROTEC 5 7SA87 (CP300), SIPROTEC 5 7SD82 (CP100), SIPROTEC 5 7SD82 (CP150), SIPROTEC 5 7SD86 (CP300), SIPROTEC 5 7SD87 (CP300), SIPROTEC 5 7SJ81 (CP100), SIPROTEC 5 7SJ81 (CP150), SIPROTEC 5 7SJ82 (CP100), SIPROTEC 5 7SJ82 (CP150), SIPROTEC 5 7SJ85 (CP300), SIPROTEC 5 7SJ86 (CP300), SIPROTEC 5 7SK82 (CP100), SIPROTEC 5 7SK82 (CP150), SIPROTEC 5 7SK85 (CP300), SIPROTEC 5 7SL82 (CP100), SIPROTEC 5 7SL82 (CP150), SIPROTEC 5 7SL86 (CP300), SIPROTEC 5 7SL87 (CP300), SIPROTEC 5 7SS85 (CP300), SIPROTEC 5 7ST85 (CP300), SIPROTEC 5 7ST86 (CP300), SIPROTEC 5 7SX82 (CP150), SIPROTEC 5 7SX85 (CP300), SIPROTEC 5 7SY82 (CP150), SIPROTEC 5 7UM85 (CP300), SIPROTEC 5 7UT82 (CP100), SIPROTEC 5 7UT82 (CP150), SIPROTEC 5 7UT85 (CP300), SIPROTEC 5 7UT86 (CP300), SIPROTEC 5 7UT87 (CP300), SIPROTEC 5 7VE85 (CP300), SIPROTEC 5 7VK87 (CP300), SIPROTEC 5 7VU85 (CP300), SIPROTEC 5 Compact 7SX800 (CP050): Currently no fix is available.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-111547 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.

5. UPDATE HISTORY

  • February 13, 2025: Initial Publication

 Read More

mySCADA myPRO Manager

 ​View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 10.0
ATTENTION: Exploitable remotely/low attack complexity
Vendor: mySCADA
Equipment: myPRO Manager
Vulnerabilities: OS Command Injection, Missing Authentication for Critical Function, Cleartext Storage of Sensitive Information, Cross-Site Request Forgery (CSRF)

2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to execute arbitrary OS commands, upload files, and obtain sensitive information without providing associated credentials.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following mySCADA products are affected:

myPRO Manager: Versions prior to 1.4

3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS Command (‘OS COMMAND INJECTION’) CWE-78
The affected product is vulnerable to an OS command injection which could allow a remote attacker to execute arbitrary OS commands.
CVE-2025-25067 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-25067. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.2.2 MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306
The administrative web interface can be accessed without authentication which could allow an unauthorized attacker to retrieve sensitive information and upload files without the associated password.
CVE-2025-24865 has been assigned to this vulnerability. A CVSS v3.1 base score of 10.0 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-24865. A base score of 10.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H).
3.2.3 CLEARTEXT STORAGE OF SENSITIVE INFORMATION CWE-312
The affected product stores credentials in cleartext, which could allow an attacker to obtain sensitive information.
CVE-2025-22896 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.6 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N).
A CVSS v4 score has also been calculated for CVE-2025-22896. A base score of 9.2 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:H/SI:N/SA:N).
3.2.4 CROSS-SITE REQUEST FORGERY (CSRF) CWE-352
The affected product is vulnerable to cross-site request forgery (CSRF), which could allow an attacker to obtain sensitive information. An attacker would need to trick the victim in to visiting an attacker-controlled website.
CVE-2025-23411 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.3 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L).
A CVSS v4 score has also been calculated for CVE-2025-23411. A base score of 5.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:A/VC:L/VI:L/VA:L/SC:N/SI:N/SA:N).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Czech Republic

3.4 RESEARCHER
Michael Heinzl reported these vulnerabilities to CISA.
4. MITIGATIONS
mySCADA recommends users update to myPRO Manager v1.4
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:

Do not click web links or open attachments in unsolicited email messages.
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY

February 13, 2025: Initial Publication 

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 10.0
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: mySCADA
  • Equipment: myPRO Manager
  • Vulnerabilities: OS Command Injection, Missing Authentication for Critical Function, Cleartext Storage of Sensitive Information, Cross-Site Request Forgery (CSRF)

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to execute arbitrary OS commands, upload files, and obtain sensitive information without providing associated credentials.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following mySCADA products are affected:

  • myPRO Manager: Versions prior to 1.4

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS Command (‘OS COMMAND INJECTION’) CWE-78

The affected product is vulnerable to an OS command injection which could allow a remote attacker to execute arbitrary OS commands.

CVE-2025-25067 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-25067. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306

The administrative web interface can be accessed without authentication which could allow an unauthorized attacker to retrieve sensitive information and upload files without the associated password.

CVE-2025-24865 has been assigned to this vulnerability. A CVSS v3.1 base score of 10.0 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-24865. A base score of 10.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H).

3.2.3 CLEARTEXT STORAGE OF SENSITIVE INFORMATION CWE-312

The affected product stores credentials in cleartext, which could allow an attacker to obtain sensitive information.

CVE-2025-22896 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.6 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2025-22896. A base score of 9.2 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:H/SI:N/SA:N).

3.2.4 CROSS-SITE REQUEST FORGERY (CSRF) CWE-352

The affected product is vulnerable to cross-site request forgery (CSRF), which could allow an attacker to obtain sensitive information. An attacker would need to trick the victim in to visiting an attacker-controlled website.

CVE-2025-23411 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.3 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L).

A CVSS v4 score has also been calculated for CVE-2025-23411. A base score of 5.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:A/VC:L/VI:L/VA:L/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Czech Republic

3.4 RESEARCHER

Michael Heinzl reported these vulnerabilities to CISA.

4. MITIGATIONS

mySCADA recommends users update to myPRO Manager v1.4

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • February 13, 2025: Initial Publication

 Read More

Siemens SIPROTEC 5

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 7.0
ATTENTION: Low attack complexity
Vendor: Siemens
Equipment: SIPROTEC 5
Vulnerability: Active Debug Code

2. RISK EVALUATION
Successful exploitation of this vulnerability could allow an unauthenticated attacker with physical access to an affected device to execute arbitrary commands on the device.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports that the following products are affected:

Siemens SIPROTEC 5 7SK85 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7SJ81 (CP100): All versions
Siemens SIPROTEC 5 7SL86 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7SL86 (CP200): All versions
Siemens SIPROTEC 5 7SJ86 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7SK82 (CP100): All versions
Siemens SIPROTEC 5 6MD84 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7SA87 (CP200): All versions
Siemens SIPROTEC 5 7ST85 (CP300): All versions
Siemens SIPROTEC 5 7SD87 (CP200): All versions
Siemens SIPROTEC 5 7UT87 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 6MD89 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7SD82 (CP100): All versions
Siemens SIPROTEC 5 6MD85 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7ST86 (CP300): All versions
Siemens SIPROTEC 5 7SJ82 (CP150): All versions prior to V9.90
Siemens SIPROTEC 5 7UT86 (CP200): All versions
Siemens SIPROTEC 5 7SX85 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7SD87 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7VU85 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 6MU85 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7SD86 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7UT86 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7VK87 (CP200): All versions
Siemens SIPROTEC 5 7UT85 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7UT82 (CP150): All versions prior to V9.90
Siemens SIPROTEC 5 7SA87 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7SJ81 (CP150): All versions prior to V9.90
Siemens SIPROTEC 5 7SJ82 (CP100): All versions
Siemens SIPROTEC 5 7SA82 (CP100): All versions
Siemens SIPROTEC 5 7UT87 (CP200): All versions
Siemens SIPROTEC 5 7SX82 (CP150): All versions prior to V9.90
Siemens SIPROTEC 5 7SD86 (CP200): All versions
Siemens SIPROTEC 5 7SL87 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 6MD85 (CP200): All versions
Siemens SIPROTEC 5 7ST85 (CP200): All versions
Siemens SIPROTEC 5 Compact 7SX800 (CP050): All versions prior to V9.90
Siemens SIPROTEC 5 6MD86 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7SD82 (CP150): All versions prior to V9.90
Siemens SIPROTEC 5 7KE85 (CP300): All versions
Siemens SIPROTEC 5 7SL82 (CP100): All versions
Siemens SIPROTEC 5 7SL82 (CP150): All versions prior to V9.90
Siemens SIPROTEC 5 7VE85 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7KE85 (CP200): All versions
Siemens SIPROTEC 5 7SA86 (CP200): All versions
Siemens SIPROTEC 5 7SL87 (CP200): All versions
Siemens SIPROTEC 5 7SY82 (CP150): All versions prior to V9.90
Siemens SIPROTEC 5 6MD86 (CP200): All versions
Siemens SIPROTEC 5 7SJ86 (CP200): All versions
Siemens SIPROTEC 5 7SA86 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7UM85 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7SS85 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7SK82 (CP150): All versions prior to V9.90
Siemens SIPROTEC 5 7UT82 (CP100): All versions
Siemens SIPROTEC 5 7SS85 (CP200): All versions
Siemens SIPROTEC 5 7SJ85 (CP200): All versions
Siemens SIPROTEC 5 7UT85 (CP200): All versions
Siemens SIPROTEC 5 7SK85 (CP200): All versions
Siemens SIPROTEC 5 7VK87 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7SJ85 (CP300): All versions prior to V9.90
Siemens SIPROTEC 5 7SA82 (CP150): All versions prior to V9.90

3.2 VULNERABILITY OVERVIEW
3.2.1 ACTIVE DEBUG CODE CWE-489
Affected devices do not properly limit access to a development shell accessible over a physical interface. This could allow an unauthenticated attacker with physical access to the device to execute arbitrary commands on the device.
CVE-2024-53648 has been assigned to this vulnerability. A CVSS v3 base score of 6.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2024-53648. A base score of 7.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Energy
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
Steffen Robertz, Stefan Viehböck, and Constantin Schieber-Knöbl from SEC Consult Vulnerability Lab reported this vulnerability to Siemens.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

All affected products: Restrict physical access to authorized individuals only to limit exposure
SIPROTEC 5 6MD85 (CP200), SIPROTEC 5 6MD86 (CP200), SIPROTEC 5 7KE85 (CP200), SIPROTEC 5 7SA86 (CP200), SIPROTEC 5 7SA87 (CP200), SIPROTEC 5 7SD86 (CP200), SIPROTEC 5 7SD87 (CP200), SIPROTEC 5 7SJ85 (CP200), SIPROTEC 5 7SJ86 (CP200), SIPROTEC 5 7SK85 (CP200), SIPROTEC 5 7SL86 (CP200), SIPROTEC 5 7SL87 (CP200), SIPROTEC 5 7SS85 (CP200), SIPROTEC 5 7ST85 (CP200), SIPROTEC 5 7UT85 (CP200), SIPROTEC 5 7UT86 (CP200), SIPROTEC 5 7UT87 (CP200), SIPROTEC 5 7VK87 (CP200): Currently no fix is planned
SIPROTEC 5 7KE85 (CP300), SIPROTEC 5 7SA82 (CP100), SIPROTEC 5 7SD82 (CP100), SIPROTEC 5 7SJ81 (CP100), SIPROTEC 5 7SJ82 (CP100), SIPROTEC 5 7SK82 (CP100), SIPROTEC 5 7SL82 (CP100), SIPROTEC 5 7ST85 (CP300), SIPROTEC 5 7ST86 (CP300), SIPROTEC 5 7UT82 (CP100): Currently no fix is available
SIPROTEC 5 Compact 7SX800 (CP050): Update to V9.90 or later version.
SIPROTEC 5 7SA82 (CP150), SIPROTEC 5 7SD82 (CP150), SIPROTEC 5 7SJ81 (CP150), SIPROTEC 5 7SJ82 (CP150), SIPROTEC 5 7SK82 (CP150), SIPROTEC 5 7SL82 (CP150), SIPROTEC 5 7SX82 (CP150), SIPROTEC 5 7SY82 (CP150), SIPROTEC 5 7UT82 (CP150): Update to V9.90 or later version.
SIPROTEC 5 6MD84 (CP300), SIPROTEC 5 6MD85 (CP300), SIPROTEC 5 6MD86 (CP300), SIPROTEC 5 6MD89 (CP300), SIPROTEC 5 6MU85 (CP300), SIPROTEC 5 7SA86 (CP300), SIPROTEC 5 7SA87 (CP300), SIPROTEC 5 7SD86 (CP300), SIPROTEC 5 7SD87 (CP300), SIPROTEC 5 7SJ85 (CP300), SIPROTEC 5 7SJ86 (CP300), SIPROTEC 5 7SK85 (CP300), SIPROTEC 5 7SL86 (CP300), SIPROTEC 5 7SL87 (CP300), SIPROTEC 5 7SS85 (CP300), SIPROTEC 5 7SX85 (CP300), SIPROTEC 5 7UM85 (CP300), SIPROTEC 5 7UT85 (CP300), SIPROTEC 5 7UT86 (CP300), SIPROTEC 5 7UT87 (CP300), SIPROTEC 5 7VE85 (CP300), SIPROTEC 5 7VK87 (CP300), SIPROTEC 5 7VU85 (CP300): Update to V9.90 or later version.

Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid’s reliability can thus be minimized by virtue of the grid design. Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.
Siemens recommends following grid security guidelines.
For more information see the associated Siemens security advisory SSA-687955 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.
5. UPDATE HISTORY

February 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.0
  • ATTENTION: Low attack complexity
  • Vendor: Siemens
  • Equipment: SIPROTEC 5
  • Vulnerability: Active Debug Code

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an unauthenticated attacker with physical access to an affected device to execute arbitrary commands on the device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • Siemens SIPROTEC 5 7SK85 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SJ81 (CP100): All versions
  • Siemens SIPROTEC 5 7SL86 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SL86 (CP200): All versions
  • Siemens SIPROTEC 5 7SJ86 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SK82 (CP100): All versions
  • Siemens SIPROTEC 5 6MD84 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SA87 (CP200): All versions
  • Siemens SIPROTEC 5 7ST85 (CP300): All versions
  • Siemens SIPROTEC 5 7SD87 (CP200): All versions
  • Siemens SIPROTEC 5 7UT87 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 6MD89 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SD82 (CP100): All versions
  • Siemens SIPROTEC 5 6MD85 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7ST86 (CP300): All versions
  • Siemens SIPROTEC 5 7SJ82 (CP150): All versions prior to V9.90
  • Siemens SIPROTEC 5 7UT86 (CP200): All versions
  • Siemens SIPROTEC 5 7SX85 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SD87 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7VU85 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 6MU85 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SD86 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7UT86 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7VK87 (CP200): All versions
  • Siemens SIPROTEC 5 7UT85 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7UT82 (CP150): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SA87 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SJ81 (CP150): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SJ82 (CP100): All versions
  • Siemens SIPROTEC 5 7SA82 (CP100): All versions
  • Siemens SIPROTEC 5 7UT87 (CP200): All versions
  • Siemens SIPROTEC 5 7SX82 (CP150): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SD86 (CP200): All versions
  • Siemens SIPROTEC 5 7SL87 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 6MD85 (CP200): All versions
  • Siemens SIPROTEC 5 7ST85 (CP200): All versions
  • Siemens SIPROTEC 5 Compact 7SX800 (CP050): All versions prior to V9.90
  • Siemens SIPROTEC 5 6MD86 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SD82 (CP150): All versions prior to V9.90
  • Siemens SIPROTEC 5 7KE85 (CP300): All versions
  • Siemens SIPROTEC 5 7SL82 (CP100): All versions
  • Siemens SIPROTEC 5 7SL82 (CP150): All versions prior to V9.90
  • Siemens SIPROTEC 5 7VE85 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7KE85 (CP200): All versions
  • Siemens SIPROTEC 5 7SA86 (CP200): All versions
  • Siemens SIPROTEC 5 7SL87 (CP200): All versions
  • Siemens SIPROTEC 5 7SY82 (CP150): All versions prior to V9.90
  • Siemens SIPROTEC 5 6MD86 (CP200): All versions
  • Siemens SIPROTEC 5 7SJ86 (CP200): All versions
  • Siemens SIPROTEC 5 7SA86 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7UM85 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SS85 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SK82 (CP150): All versions prior to V9.90
  • Siemens SIPROTEC 5 7UT82 (CP100): All versions
  • Siemens SIPROTEC 5 7SS85 (CP200): All versions
  • Siemens SIPROTEC 5 7SJ85 (CP200): All versions
  • Siemens SIPROTEC 5 7UT85 (CP200): All versions
  • Siemens SIPROTEC 5 7SK85 (CP200): All versions
  • Siemens SIPROTEC 5 7VK87 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SJ85 (CP300): All versions prior to V9.90
  • Siemens SIPROTEC 5 7SA82 (CP150): All versions prior to V9.90

3.2 VULNERABILITY OVERVIEW

3.2.1 ACTIVE DEBUG CODE CWE-489

Affected devices do not properly limit access to a development shell accessible over a physical interface. This could allow an unauthenticated attacker with physical access to the device to execute arbitrary commands on the device.

CVE-2024-53648 has been assigned to this vulnerability. A CVSS v3 base score of 6.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-53648. A base score of 7.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Steffen Robertz, Stefan Viehböck, and Constantin Schieber-Knöbl from SEC Consult Vulnerability Lab reported this vulnerability to Siemens.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • All affected products: Restrict physical access to authorized individuals only to limit exposure
  • SIPROTEC 5 6MD85 (CP200), SIPROTEC 5 6MD86 (CP200), SIPROTEC 5 7KE85 (CP200), SIPROTEC 5 7SA86 (CP200), SIPROTEC 5 7SA87 (CP200), SIPROTEC 5 7SD86 (CP200), SIPROTEC 5 7SD87 (CP200), SIPROTEC 5 7SJ85 (CP200), SIPROTEC 5 7SJ86 (CP200), SIPROTEC 5 7SK85 (CP200), SIPROTEC 5 7SL86 (CP200), SIPROTEC 5 7SL87 (CP200), SIPROTEC 5 7SS85 (CP200), SIPROTEC 5 7ST85 (CP200), SIPROTEC 5 7UT85 (CP200), SIPROTEC 5 7UT86 (CP200), SIPROTEC 5 7UT87 (CP200), SIPROTEC 5 7VK87 (CP200): Currently no fix is planned
  • SIPROTEC 5 7KE85 (CP300), SIPROTEC 5 7SA82 (CP100), SIPROTEC 5 7SD82 (CP100), SIPROTEC 5 7SJ81 (CP100), SIPROTEC 5 7SJ82 (CP100), SIPROTEC 5 7SK82 (CP100), SIPROTEC 5 7SL82 (CP100), SIPROTEC 5 7ST85 (CP300), SIPROTEC 5 7ST86 (CP300), SIPROTEC 5 7UT82 (CP100): Currently no fix is available
  • SIPROTEC 5 Compact 7SX800 (CP050): Update to V9.90 or later version.
  • SIPROTEC 5 7SA82 (CP150), SIPROTEC 5 7SD82 (CP150), SIPROTEC 5 7SJ81 (CP150), SIPROTEC 5 7SJ82 (CP150), SIPROTEC 5 7SK82 (CP150), SIPROTEC 5 7SL82 (CP150), SIPROTEC 5 7SX82 (CP150), SIPROTEC 5 7SY82 (CP150), SIPROTEC 5 7UT82 (CP150): Update to V9.90 or later version.
  • SIPROTEC 5 6MD84 (CP300), SIPROTEC 5 6MD85 (CP300), SIPROTEC 5 6MD86 (CP300), SIPROTEC 5 6MD89 (CP300), SIPROTEC 5 6MU85 (CP300), SIPROTEC 5 7SA86 (CP300), SIPROTEC 5 7SA87 (CP300), SIPROTEC 5 7SD86 (CP300), SIPROTEC 5 7SD87 (CP300), SIPROTEC 5 7SJ85 (CP300), SIPROTEC 5 7SJ86 (CP300), SIPROTEC 5 7SK85 (CP300), SIPROTEC 5 7SL86 (CP300), SIPROTEC 5 7SL87 (CP300), SIPROTEC 5 7SS85 (CP300), SIPROTEC 5 7SX85 (CP300), SIPROTEC 5 7UM85 (CP300), SIPROTEC 5 7UT85 (CP300), SIPROTEC 5 7UT86 (CP300), SIPROTEC 5 7UT87 (CP300), SIPROTEC 5 7VE85 (CP300), SIPROTEC 5 7VK87 (CP300), SIPROTEC 5 7VU85 (CP300): Update to V9.90 or later version.

Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid’s reliability can thus be minimized by virtue of the grid design. Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.

Siemens recommends following grid security guidelines.

For more information see the associated Siemens security advisory SSA-687955 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.

5. UPDATE HISTORY

  • February 13, 2025: Initial Publication

 Read More

Siemens SIMATIC S7-1200 CPU Family

 ​As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).
View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 8.7
ATTENTION: Exploitable remotely/low attack complexity
Vendor: Siemens
Equipment: SIMATIC S7-1200 CPU Family
Vulnerabilities: Improper Resource Shutdown or Release, Improper Validation of Syntactic Correctness of Input

2. RISK EVALUATION
The affected devices do not correctly process certain special crafted packets sent to Port 80/tcp and Port 102/tcp, which could allow an attacker to cause a denial of service in the device.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
Siemens reports the following products are affected:

Siemens SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-2XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-2XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1214FC DC/DC/DC (6AG1214-1AF40-5XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1214C DC/DC/DC RAIL (6AG2214-1AG40-1XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-5XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-2XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1211C AC/DC/Rly (6ES7211-1BE40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1215C AC/DC/Rly (6ES7215-1BG40-0XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-4XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-2XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1212C DC/DC/Rly (6ES7212-1HE40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1215C DC/DC/Rly (6ES7215-1HG40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1211C DC/DC/Rly (6ES7211-1HE40-0XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-2XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-4XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-5XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-4XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1212FC DC/DC/DC (6ES7212-1AF40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1217C DC/DC/DC (6ES7217-1AG40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1215C DC/DC/DC (6ES7215-1AG40-0XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-4XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-2XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1214C DC/DC/DC (6ES7214-1AG40-0XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-4XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1215FC DC/DC/Rly (6ES7215-1HF40-0XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-2XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1211C DC/DC/DC (6ES7211-1AE40-0XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-2XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1212C DC/DC/DC (6ES7212-1AE40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1215FC DC/DC/DC (6ES7215-1AF40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1214C AC/DC/Rly (6ES7214-1BG40-0XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-4XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-5XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1212FC DC/DC/Rly (6ES7212-1HF40-0XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1214FC DC/DC/DC (6ES7214-1AF40-0XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1214FC DC/DC/RLY (6AG1214-1HF40-5XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1215C DC/DC/DC (6AG1215-1AG40-5XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1212C AC/DC/Rly (6ES7212-1BE40-0XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-4XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1214FC DC/DC/Rly (6ES7214-1HF40-0XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1215FC DC/DC/DC (6AG1215-1AF40-5XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-5XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-4XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-4XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1212C DC/DC/DC RAIL (6AG2212-1AE40-1XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-5XB0): vers:all/<V4.7
Siemens SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-2XB0): vers:all/<V4.7
Siemens SIMATIC S7-1200 CPU 1214C DC/DC/Rly (6ES7214-1HG40-0XB0): vers:all/<V4.7

3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER RESOURCE SHUTDOWN OR RELEASE CWE-404
The affected devices do not correctly process certain special crafted packets sent to Port 80/tcp, which could allow an unauthenticated attacker to cause a denial of service in the device.
CVE-2025-24811 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2025-24811. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.2.2 IMPROPER VALIDATION OF SYNTACTIC CORRECTNESS OF INPUT CWE-1286
The affected devices do not correctly process certain special crafted packets sent to Port 102/tcp, which could allow an attacker to cause a denial of service in the device.
CVE-2025-24812 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).
A CVSS v4 score has also been calculated for CVE-2025-24812. A base score of 7.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER
Gao Jian coordinated the disclosure of CVE-2025-24812 with Siemens.Siemens then reported these vulnerabilities to CISA.
4. MITIGATIONS
Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-2XB0), SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-4XB0), SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-2XB0), SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-4XB0), SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-2XB0), SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-4XB0), SIPLUS S7-1200 CPU 1212C DC/DC/DC RAIL (6AG2212-1AE40-1XB0), SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-2XB0), SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-4XB0), SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-5XB0), SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-2XB0), SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-4XB0), SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-5XB0), SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-2XB0), SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-4XB0), SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-5XB0), SIPLUS S7-1200 CPU 1214C DC/DC/DC RAIL (6AG2214-1AG40-1XB0), SIPLUS S7-1200 CPU 1214FC DC/DC/DC (6AG1214-1AF40-5XB0), SIPLUS S7-1200 CPU 1214FC DC/DC/RLY (6AG1214-1HF40-5XB0), SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-2XB0), SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-4XB0), SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-5XB0), SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-2XB0), SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-4XB0), SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-2XB0), SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-4XB0), SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-5XB0), SIPLUS S7-1200 CPU 1215C DC/DC/DC (6AG1215-1AG40-5XB0), SIPLUS S7-1200 CPU 1215FC DC/DC/DC (6AG1215-1AF40-5XB0): Update to V4.7 or a later version.
SIMATIC S7-1200 CPU 1211C AC/DC/Rly (6ES7211-1BE40-0XB0), SIMATIC S7-1200 CPU 1211C DC/DC/DC (6ES7211-1AE40-0XB0), SIMATIC S7-1200 CPU 1211C DC/DC/Rly (6ES7211-1HE40-0XB0), SIMATIC S7-1200 CPU 1212C AC/DC/Rly (6ES7212-1BE40-0XB0), SIMATIC S7-1200 CPU 1212C DC/DC/DC (6ES7212-1AE40-0XB0), SIMATIC S7-1200 CPU 1212C DC/DC/Rly (6ES7212-1HE40-0XB0), SIMATIC S7-1200 CPU 1212FC DC/DC/DC (6ES7212-1AF40-0XB0), SIMATIC S7-1200 CPU 1212FC DC/DC/Rly (6ES7212-1HF40-0XB0), SIMATIC S7-1200 CPU 1214C AC/DC/Rly (6ES7214-1BG40-0XB0), SIMATIC S7-1200 CPU 1214C DC/DC/DC (6ES7214-1AG40-0XB0), SIMATIC S7-1200 CPU 1214C DC/DC/Rly (6ES7214-1HG40-0XB0), SIMATIC S7-1200 CPU 1214FC DC/DC/DC (6ES7214-1AF40-0XB0), SIMATIC S7-1200 CPU 1214FC DC/DC/Rly (6ES7214-1HF40-0XB0), SIMATIC S7-1200 CPU 1215C AC/DC/Rly (6ES7215-1BG40-0XB0), SIMATIC S7-1200 CPU 1215C DC/DC/DC (6ES7215-1AG40-0XB0), SIMATIC S7-1200 CPU 1215C DC/DC/Rly (6ES7215-1HG40-0XB0), SIMATIC S7-1200 CPU 1215FC DC/DC/DC (6ES7215-1AF40-0XB0), SIMATIC S7-1200 CPU 1215FC DC/DC/Rly (6ES7215-1HF40-0XB0), SIMATIC S7-1200 CPU 1217C DC/DC/DC (6ES7217-1AG40-0XB0): Update to V4.7 or a later version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.
Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.
For more information see the associated Siemens security advisory SSA-224824 in HTML and CSAF.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY

February 13, 2025: Initial Publication 

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SIMATIC S7-1200 CPU Family
  • Vulnerabilities: Improper Resource Shutdown or Release, Improper Validation of Syntactic Correctness of Input

2. RISK EVALUATION

The affected devices do not correctly process certain special crafted packets sent to Port 80/tcp and Port 102/tcp, which could allow an attacker to cause a denial of service in the device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports the following products are affected:

  • Siemens SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-2XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-2XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1214FC DC/DC/DC (6AG1214-1AF40-5XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1214C DC/DC/DC RAIL (6AG2214-1AG40-1XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-5XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-2XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1211C AC/DC/Rly (6ES7211-1BE40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1215C AC/DC/Rly (6ES7215-1BG40-0XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-4XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-2XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1212C DC/DC/Rly (6ES7212-1HE40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1215C DC/DC/Rly (6ES7215-1HG40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1211C DC/DC/Rly (6ES7211-1HE40-0XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-2XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-4XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-5XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-4XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1212FC DC/DC/DC (6ES7212-1AF40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1217C DC/DC/DC (6ES7217-1AG40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1215C DC/DC/DC (6ES7215-1AG40-0XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-4XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-2XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1214C DC/DC/DC (6ES7214-1AG40-0XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-4XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1215FC DC/DC/Rly (6ES7215-1HF40-0XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-2XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1211C DC/DC/DC (6ES7211-1AE40-0XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-2XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1212C DC/DC/DC (6ES7212-1AE40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1215FC DC/DC/DC (6ES7215-1AF40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1214C AC/DC/Rly (6ES7214-1BG40-0XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-4XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-5XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1212FC DC/DC/Rly (6ES7212-1HF40-0XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1214FC DC/DC/DC (6ES7214-1AF40-0XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1214FC DC/DC/RLY (6AG1214-1HF40-5XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1215C DC/DC/DC (6AG1215-1AG40-5XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1212C AC/DC/Rly (6ES7212-1BE40-0XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-4XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1214FC DC/DC/Rly (6ES7214-1HF40-0XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1215FC DC/DC/DC (6AG1215-1AF40-5XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-5XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-4XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-4XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1212C DC/DC/DC RAIL (6AG2212-1AE40-1XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-5XB0): vers:all/<V4.7
  • Siemens SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-2XB0): vers:all/<V4.7
  • Siemens SIMATIC S7-1200 CPU 1214C DC/DC/Rly (6ES7214-1HG40-0XB0): vers:all/<V4.7

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER RESOURCE SHUTDOWN OR RELEASE CWE-404

The affected devices do not correctly process certain special crafted packets sent to Port 80/tcp, which could allow an unauthenticated attacker to cause a denial of service in the device.

CVE-2025-24811 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-24811. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.2.2 IMPROPER VALIDATION OF SYNTACTIC CORRECTNESS OF INPUT CWE-1286

The affected devices do not correctly process certain special crafted packets sent to Port 102/tcp, which could allow an attacker to cause a denial of service in the device.

CVE-2025-24812 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-24812. A base score of 7.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Gao Jian coordinated the disclosure of CVE-2025-24812 with Siemens.
Siemens then reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-2XB0), SIPLUS S7-1200 CPU 1212 AC/DC/RLY (6AG1212-1BE40-4XB0), SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-2XB0), SIPLUS S7-1200 CPU 1212 DC/DC/RLY (6AG1212-1HE40-4XB0), SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-2XB0), SIPLUS S7-1200 CPU 1212C DC/DC/DC (6AG1212-1AE40-4XB0), SIPLUS S7-1200 CPU 1212C DC/DC/DC RAIL (6AG2212-1AE40-1XB0), SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-2XB0), SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-4XB0), SIPLUS S7-1200 CPU 1214 AC/DC/RLY (6AG1214-1BG40-5XB0), SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-2XB0), SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-4XB0), SIPLUS S7-1200 CPU 1214 DC/DC/DC (6AG1214-1AG40-5XB0), SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-2XB0), SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-4XB0), SIPLUS S7-1200 CPU 1214 DC/DC/RLY (6AG1214-1HG40-5XB0), SIPLUS S7-1200 CPU 1214C DC/DC/DC RAIL (6AG2214-1AG40-1XB0), SIPLUS S7-1200 CPU 1214FC DC/DC/DC (6AG1214-1AF40-5XB0), SIPLUS S7-1200 CPU 1214FC DC/DC/RLY (6AG1214-1HF40-5XB0), SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-2XB0), SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-4XB0), SIPLUS S7-1200 CPU 1215 AC/DC/RLY (6AG1215-1BG40-5XB0), SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-2XB0), SIPLUS S7-1200 CPU 1215 DC/DC/DC (6AG1215-1AG40-4XB0), SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-2XB0), SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-4XB0), SIPLUS S7-1200 CPU 1215 DC/DC/RLY (6AG1215-1HG40-5XB0), SIPLUS S7-1200 CPU 1215C DC/DC/DC (6AG1215-1AG40-5XB0), SIPLUS S7-1200 CPU 1215FC DC/DC/DC (6AG1215-1AF40-5XB0): Update to V4.7 or a later version.
  • SIMATIC S7-1200 CPU 1211C AC/DC/Rly (6ES7211-1BE40-0XB0), SIMATIC S7-1200 CPU 1211C DC/DC/DC (6ES7211-1AE40-0XB0), SIMATIC S7-1200 CPU 1211C DC/DC/Rly (6ES7211-1HE40-0XB0), SIMATIC S7-1200 CPU 1212C AC/DC/Rly (6ES7212-1BE40-0XB0), SIMATIC S7-1200 CPU 1212C DC/DC/DC (6ES7212-1AE40-0XB0), SIMATIC S7-1200 CPU 1212C DC/DC/Rly (6ES7212-1HE40-0XB0), SIMATIC S7-1200 CPU 1212FC DC/DC/DC (6ES7212-1AF40-0XB0), SIMATIC S7-1200 CPU 1212FC DC/DC/Rly (6ES7212-1HF40-0XB0), SIMATIC S7-1200 CPU 1214C AC/DC/Rly (6ES7214-1BG40-0XB0), SIMATIC S7-1200 CPU 1214C DC/DC/DC (6ES7214-1AG40-0XB0), SIMATIC S7-1200 CPU 1214C DC/DC/Rly (6ES7214-1HG40-0XB0), SIMATIC S7-1200 CPU 1214FC DC/DC/DC (6ES7214-1AF40-0XB0), SIMATIC S7-1200 CPU 1214FC DC/DC/Rly (6ES7214-1HF40-0XB0), SIMATIC S7-1200 CPU 1215C AC/DC/Rly (6ES7215-1BG40-0XB0), SIMATIC S7-1200 CPU 1215C DC/DC/DC (6ES7215-1AG40-0XB0), SIMATIC S7-1200 CPU 1215C DC/DC/Rly (6ES7215-1HG40-0XB0), SIMATIC S7-1200 CPU 1215FC DC/DC/DC (6ES7215-1AF40-0XB0), SIMATIC S7-1200 CPU 1215FC DC/DC/Rly (6ES7215-1HF40-0XB0), SIMATIC S7-1200 CPU 1217C DC/DC/DC (6ES7217-1AG40-0XB0): Update to V4.7 or a later version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-224824 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • February 13, 2025: Initial Publication

 Read More

Outback Power Mojave Inverter

 ​View CSAF
1. EXECUTIVE SUMMARY

CVSS v4 8.7
ATTENTION: Exploitable remotely/low attack complexity
Vendor: Outback Power
Equipment: Mojave Inverter
Vulnerabilities: Use of GET Request Method With Sensitive Query Strings, Exposure of Sensitive Information to an Unauthorized Actor, Command Injection

2. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow an attacker to access sensitive data or inject commands.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of Outback Power Mojave Inverter, a system for managing power in a residential grid-connected battery backup system, are affected:

Outback Power Mojave Inverter: All versions

3.2 VU;NERABILITY OVERVIEW
3.2.1 Use of GET Request Method With Sensitive Query Strings CWE-598
The Mojave Inverter uses the GET method for sensitive information.
CVE-2025-26473 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).
A CVSS v4 score has also been calculated forCVE-2025-26473. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).
3.2.2 Exposure of Sensitive Information to an Unauthorized Actor CWE-200
An attacker may modify the URL to discover sensitive information about the target network.
CVE-2025-25281 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).
A CVSS v4 score has also been calculated forCVE-2025-25281. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).
3.2.3 Improper Neutralization of Special Elements used in a Command CWE-77
An attacker may inject commands via specially-crafted post requests.
CVE-2025-24861 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).
A CVSS v4 score has also been calculated forCVE-2025-24861. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).
3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Energy
COUNTRIES/AREAS DEPLOYED: United States
COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER
Jon Hurtado of Sandia National Laboratory reported these vulnerabilities to CISA.
4. MITIGATIONS
The Mojave Inverter was a product of Enersys. When Outback Power was split off from Enersys recently, Mojave Inverter was moved to Outback Power, but without the resources to maintain the product. Outback Power may discontinue this product and has not yet addressed these vulnerabilities. CISA recommends disabling the networking features of this product until a replacement product can be acquired.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

Disable un-used functions.
Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:

Do not click web links or open attachments in unsolicited email messages.
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
5. UPDATE HISTORY

February 13, 2025: Initial Publication 

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Outback Power
  • Equipment: Mojave Inverter
  • Vulnerabilities: Use of GET Request Method With Sensitive Query Strings, Exposure of Sensitive Information to an Unauthorized Actor, Command Injection

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to access sensitive data or inject commands.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Outback Power Mojave Inverter, a system for managing power in a residential grid-connected battery backup system, are affected:

  • Outback Power Mojave Inverter: All versions

3.2 VU;NERABILITY OVERVIEW

3.2.1 Use of GET Request Method With Sensitive Query Strings CWE-598

The Mojave Inverter uses the GET method for sensitive information.

CVE-2025-26473 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated forCVE-2025-26473. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.2.2 Exposure of Sensitive Information to an Unauthorized Actor CWE-200

An attacker may modify the URL to discover sensitive information about the target network.

CVE-2025-25281 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated forCVE-2025-25281. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.2.3 Improper Neutralization of Special Elements used in a Command CWE-77

An attacker may inject commands via specially-crafted post requests.

CVE-2025-24861 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated forCVE-2025-24861. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy
  • COUNTRIES/AREAS DEPLOYED: United States
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Jon Hurtado of Sandia National Laboratory reported these vulnerabilities to CISA.

4. MITIGATIONS

The Mojave Inverter was a product of Enersys. When Outback Power was split off from Enersys recently, Mojave Inverter was moved to Outback Power, but without the resources to maintain the product. Outback Power may discontinue this product and has not yet addressed these vulnerabilities. CISA recommends disabling the networking features of this product until a replacement product can be acquired.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Disable un-used functions.
  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • February 13, 2025: Initial Publication

 Read More

CISA Adds Two Known Exploited Vulnerabilities to Catalog

 ​CISA has added two new vulnerabilities to its Known Exploited Vulnerabilities Catalog, based on evidence of active exploitation.

CVE-2025-24200 Apple iOS and iPadOS Incorrect Authorization Vulnerability
CVE-2024-41710 Mitel SIP Phones Argument Injection Vulnerability

These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise.
Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the Known Exploited Vulnerabilities Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information.
Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria. 

CISA has added two new vulnerabilities to its Known Exploited Vulnerabilities Catalog, based on evidence of active exploitation.

  • CVE-2025-24200 Apple iOS and iPadOS Incorrect Authorization Vulnerability
  • CVE-2024-41710 Mitel SIP Phones Argument Injection Vulnerability

These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise.

Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the Known Exploited Vulnerabilities Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information.

Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.

 Read More